Plan Review Notes
Plan Review Notes For Permit 07090646
Permit Number 07090646
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-20 12:13:35 
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $303.11 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL. THIS IS REQUIRED FOR SPACE THAT WILL BE
 CONDITIONED IN FUTURE
  
 5)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7)THE GLAZING THICKNESS ON THE PLANS ARE NOT PROVIDED
 IN THE PRODUCT APPROVALS FOR THE SINGLE HUNG AND FIXED
 WINDOWS OR THE SLIDING GLASS DOORS
  
 8)THERE ARE MIXED NOA'S SUPPLIED FOR THE SINGLE HUNG
 AND FIXED WINDOWS
  
 9)WINDOW DESIGNATION IN RESTROOM ON 2ND FLOOR PLAN IS
 FOR FIXED WINDOW
  
 10)PROVIDE SCHEDULE FOR ALL STRAPS/CONNECTORS THAT
 INCLUDES THEIR FLORIDA STATEWIDE PRODUCT APPROVAL
 NUMBERS OR THE SIMPSON TIE INDEX SHEET OF FLORIDA
 APPROVED CONNECTORS WITH THE PRODUCTS HIGHLIGHTED OR
 PROVIDE THE PRODUCT APPROVALS
  
 11)STRUCTURAL DRAWINGS DO NOT SHOW BLOCK TO BE
 INSTALLED AT LOCATION OF EXISTING WOOD FRAME WALL AT
 NORTH EAST CORNER OF GARAGE ON THE FOUNDATION PLAN
  
 12)PROVIDE DETAIL FOR THE ATTACHMENT OF THE STEEL
 COLUMN BASE PLATE TO THE BLOCK COLUMN AT REAR DECK.
 WILL THERE BE A CONCRETE CAP OR IS BASE PLATE MOUNTED
 DIRECTLY TO THE GROUTED FILL CELLS?
  
 13)STRUCTURAL STEEL COLUMN DESIGNATION IN SCHEDULE
 DOES NOT MATCH PLAN DESIGNATION
  
 14)GUARDS AND HANDRAILS SHALL MEET THE LOAD
 REQUIREMENTS OF 1607.7.1.1 FBC
  
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW