| 2008-08-29 16:21:03 | |
| | |
| | |
| | |
| | ** DENIED 5TH TIME** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. PLANS |
| | IN LOWER RIGHT HAND CORNER INDICATES A * AUTOMATIC |
| | TRANSFER SWITCH MTS-FMC* AND YET THE RISER STATES |
| | ***ATS-FMC**> THIS WAS GONE OVER EXTENSIVELY WITH THE |
| | ENGINEER OF RECORD PREVIOUS TO PLANS BEING RE-DONE AND |
| | RE-SUBMITTED YET THE SAME INCONSISTENCIES EXIST. THIS |
| | OFFICE OR REVIEWER HAS NO AUTHORITY TO REVISE OR ADJUST |
| | PLANS NOR DOES THIS REVIEW HAVE THE RIGHT TO REDLINED |
| | PLANS BASED ON WHAT THE ENGINEER MAY OR MAY NOT WANT AS |
| | HIS/HER DESIGN. IT IS NOT FOR THE REVIEWER TO DECIDE |
| | WHAT THE DESIGNERS INTENT IS. |
| | THIS REVIEWER HAS CALLED MR. LON CARTER AND LEFT A |
| | VOICE-MAIL AS OF THIS REVIEW. MR. CARTER IS OUT OF THE |
| | OFFICE UNTIL TUESDAY THE 2ND OF SEPT. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |