2008-07-18 12:15:14** DENIED 4TH REVIEW **
  
 ** NEW COMMENTS DUE TO ITEMS NOW CHANGED WHICH WERE NOT
 ON PREVIOUS PLANS. THERE IS ALSO ONE COMMENT WHICH HAS
 BEEN THE SAME SINCE THE INITIAL REVIEW.
  
 1) NOTE: PLEASE SEE THE NEW SPECIFICATIONS SUBMITTED
 FOR THE TRANSFER SWITCH ONLY HAS ONE COPY IN SET.
 PLEASE ALSO SEE THE SPECS SHOW THIS BEING AN AUTOMATIC
 TRANSFER SWITCH HOWEVER DETAIL LABELED AS *PART PLAN*
 ON SHEET E5.1 NOW SHOWS A MTS FOR MANUAL TRANSFER
 SWITCH AND THE RISER SHOWS ATS FOR AUTOMATIC TRANSFER
 SWITCH. IN THE LAST CONVERSATION WITH THE ENGINEER OF
 RECORD THE COMMENT WAS THE TRANSFER SWITCH WAS GOING TO
 BE MANUAL, HOWEVER APPLICATION, RISER SPECS AND OTHER
 INFORMATION INDICATES AUTOMATIC.
 WHICH ONE WILL IT BE?
 PLEASE SEE LOAD SUMMARY ON SHEET 5.2 WHICH CALLS FOR
 MAINS FOR PANELS A AND B AND A MAIN #3 FOR PANEL *C*.
 HOW ARE THE DISCONNECTS ON THE LOAD SIDE OF THE SINGLE
 MAIN SHOWN ON RISERNOW CALLED *MAINS* ON THE LOAD
 SUMMARY?
  
 PLEASE CORRECT PLANS.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 LIFE SAFETY CODE/ NFPA-101. PREVIOUS PLANS CALLED FOR A
 2005 NFPA-101 AND THE REVIEW NOTES STATED THERE WAS NO
 SUCH CODE. THE REVIEW NOTES GAVE THE CODE IN AFFECT
 WHICH WAS ADOPTED BY FS 553.73 YET THE PLANS NOW
 REFLECT A 2006 NFPA-101. HOW CAN A CODE BE REFERENCED
 ON DESIGN PLANS WHEN THE 2006 LIFE SAFETY CODE IS NOT
 SCHEDULED TO BE ADOPTED BY THE STATE OF FLORIDA UNTIL
 THE END OF 2008?
 NO JURISDICTION IS PERMITTED TO ADOPTED ANY CODE UNLESS
 ADOPTED BY THE STATE OF FLORIDA.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved