| 2008-07-18 12:15:14 | ** DENIED 4TH REVIEW ** |
| | |
| | ** NEW COMMENTS DUE TO ITEMS NOW CHANGED WHICH WERE NOT |
| | ON PREVIOUS PLANS. THERE IS ALSO ONE COMMENT WHICH HAS |
| | BEEN THE SAME SINCE THE INITIAL REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THE NEW SPECIFICATIONS SUBMITTED |
| | FOR THE TRANSFER SWITCH ONLY HAS ONE COPY IN SET. |
| | PLEASE ALSO SEE THE SPECS SHOW THIS BEING AN AUTOMATIC |
| | TRANSFER SWITCH HOWEVER DETAIL LABELED AS *PART PLAN* |
| | ON SHEET E5.1 NOW SHOWS A MTS FOR MANUAL TRANSFER |
| | SWITCH AND THE RISER SHOWS ATS FOR AUTOMATIC TRANSFER |
| | SWITCH. IN THE LAST CONVERSATION WITH THE ENGINEER OF |
| | RECORD THE COMMENT WAS THE TRANSFER SWITCH WAS GOING TO |
| | BE MANUAL, HOWEVER APPLICATION, RISER SPECS AND OTHER |
| | INFORMATION INDICATES AUTOMATIC. |
| | WHICH ONE WILL IT BE? |
| | PLEASE SEE LOAD SUMMARY ON SHEET 5.2 WHICH CALLS FOR |
| | MAINS FOR PANELS A AND B AND A MAIN #3 FOR PANEL *C*. |
| | HOW ARE THE DISCONNECTS ON THE LOAD SIDE OF THE SINGLE |
| | MAIN SHOWN ON RISERNOW CALLED *MAINS* ON THE LOAD |
| | SUMMARY? |
| | |
| | PLEASE CORRECT PLANS. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE |
| | LIFE SAFETY CODE/ NFPA-101. PREVIOUS PLANS CALLED FOR A |
| | 2005 NFPA-101 AND THE REVIEW NOTES STATED THERE WAS NO |
| | SUCH CODE. THE REVIEW NOTES GAVE THE CODE IN AFFECT |
| | WHICH WAS ADOPTED BY FS 553.73 YET THE PLANS NOW |
| | REFLECT A 2006 NFPA-101. HOW CAN A CODE BE REFERENCED |
| | ON DESIGN PLANS WHEN THE 2006 LIFE SAFETY CODE IS NOT |
| | SCHEDULED TO BE ADOPTED BY THE STATE OF FLORIDA UNTIL |
| | THE END OF 2008? |
| | NO JURISDICTION IS PERMITTED TO ADOPTED ANY CODE UNLESS |
| | ADOPTED BY THE STATE OF FLORIDA. |
| | |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |