Plan Review Notes
Plan Review Notes For Permit 07090643
Permit Number 07090643
Review Stop E
Sequence Number 3
Notes
Date Text
2008-05-22 13:42:31** DENIED 3RD REVIEW**
  
  
 1) NOTE: THE NOTES BELOW ARE THE SAME COMMENTS AS THE
 PREVIOUS REVIEW. AS THE SAME PLANS WERE RE-SUBMITTED
 WIHT NO CORRECTIONS THE SAME COMMENTS APPLY.
  
 2) NOTE: PLEASE SEE A FEE HAS NOW BEEN ASSESSED AS
 REQUIRED PER FS 553.80(2)(B) FOR REPEAT CODE COMPLIANCE
 COMMENTS.
  
 3) NOTE: PLEASE SEE ONE OF THE COMMENTS BELOW FROM
 PREVIOUS REVIEW WITH RESPECTTO VALUE WAS IN A
 RESPONSE LETTER WHICH MENTIONS VALUE FOR COMPLETE SCOPE
 WAS INCREASED HOWEVER THIS WAS NOT DONE WHEN PLANS WERE
 RESUBMITTEED. THE APPLICAITON WAS NOT CHANGED ETC. THIS
 VALUE HAS BEEN CHANGED AND FEES WILL BE DUE BEFORE
 RESUBMITTING PLANS.
  
 4) NOTE: TOTAL FEES DUE INCLUDING NOTES 2 AND 3 IS
 $5,400
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEWS WHICH ARE
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE NOT
 ACCURATE ON PLANS. IF THIS WAS THE ONLY COMMENT THESE
 COULD HAVE BEEN RED-LINED HOWEVER PLANS ARE COMING BACK
 FOR OTHER COMMENTS.
 PLEASE SEE THE FOLLOWING CODES SHALL BE STATED. 2002
 NFPA-110. (PLANS STATE 2005 NFPA-110 WHICH DOES NOT
 EXIST).
 2003 NFPA-101. (PLANS STATE 2005 NFPA-101WHICH DOES NOT
 EXIST).
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE APPLIED
 SCOPE OF DOES NOT MEET THE TABLES FOR THE SCOPE OF WORK
 FOR ALL TRADES.
 PLEASE SE RESPONSE LETTER MENTIONS THE APPLIED VALUE IS
 NOW $200K HOWEVER THE PERMIT APPLICATION, THE RE-SUB
 COVER SHEET ETC WAS NOT UPDATED,
 FBC 108.3
  
 3) NOTE: PLEASE SEE THE SPECS/MANUFACTURES CUT SHEETS
 SUBMITTED DO NOT CORRELATE WITH PLANS.
 THESE INDICATE A KOHLER ATS AND THE PLANS NOW INDICATE
 CUTLER HAMMER.
 WHICH ONE WILL BE INSTALLED?
 PLEASE SEE THAT IN EITHER CASE THE SPECIFICATIONS ON
 PLANS ARE NOT EASILY READ AND ARE *BLURRY* TO READ
 DETAILS REQUIRED.
 PLEASE SEE NEC 225.31-225.39 AS THE DISCONNECTING MEANS
 IS NOT READILY AVAILABLE BASED ON PLANS SUBMITTED.
 PLEASE SEE THE SECTIONS MENTIONED ABOVE AS THE
 DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD SERVED
 AND SHALL BE LOCATED ON THE OUTSIDE OF EQUIPMENT WITH
 OUT EXPOSING ANY INDIVIDUAL TO LIVE PARTS. 110.27.
 PLEASE SEE THE PICTURE DOES APPEAR TO SHOW TWO BREAKERS
 HOWEVER DOES NOT APPEAR TO MEET CODE AS STATED ABOVE.
 THIS IS BASED ON PLANS SUBMITTED AND THE TWO SETS OF
 DOCUMENTS.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
 ** PLANS MAY BE RETAINED BY THIS OFFICE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]