| Date |
Text |
| 2007-10-16 09:27:47 | |
| | |
| | **** DENIED **** |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW UNDER |
| | EXPIRED PERMIT ARE STILL IN NEED OF ADDRESSING. |
| | THERE ARE ALSO SOME NEW COMMENTS BASED ON |
| | PLANS/DOCUMENTS SUBMITTED. |
| | |
| | |
| | 1) NOTE:PLEASE KNOW AS THE PERMIT APPLICATION DATE |
| | HAS CHANGED. |
| | PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT CODES ARE |
| | STATED ON PLANS. |
| | PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER |
| | DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A |
| | MINIMUM. |
| | PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE |
| | REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE |
| | FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS |
| | FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (2002 SHOWN ON PLANS) |
| | |
| | IF THIS WAS THE ONLY COMMENT PLANS WOULD HAVE BEEN |
| | REDLINED, HOWEVER THEY ARE COMING BACK FOR OTHER |
| | COMMENTS. |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORKWAS STILL NOT INCREASED. THE VALUE IS REQUIRED TO |
| | BE BASED ON ALL LABOR, MATERIALS, EQUIPMENT, DESIGN |
| | COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. |
| | BASED ON ALL THE WORK AS SHOWN ON PLANS ETC THE VALUE |
| | AS APPLIED IS VERY LOW. |
| | IF AN APPROPRIATE VALUE IS NOT ADJUSTED, ONE WILL BE |
| | ASSESSED. |
| | FBC 108.3 |
| | |
| | 3) NOTE: PLEASE CLARIFY WHY THE GENERATOR SUBMITTALS |
| | CONTAIN A SEPARATE ELECTRICAL CONTRACTOR ON THE LISTING |
| | OF COVER SHEET. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | ATS SWITCHES WHICH ARE BEING SHOWN ON THE RISER. PLEASE |
| | SEE THE NEXT COMMENT FOR DISCONNECTING MEANS REQUIRED. |
| | FBC 106.1.2. |
| | NEC 90.7, 110.3. |
| | |
| | 4) NOTE: PLEASE SEE THE RISER DOES NOT INCLUDE A |
| | DISCONNECTING MEANS FOR FEEDERS COMING FROM THE |
| | GENERATOR. |
| | 225.31-225.39. |
| | (MAY NOT USE BREAKER ON THE GENERATOR AS IT DOES NOT |
| | MEET 702.11) |
| | PLEASE INCLUDE DISCONNECT/DISCONNECTS ON THE FEEDERS |
| | EITHER ON THE LINE SIDE OF GUTTER FROM GENERATOR, OR |
| | LOAD SIDE OF ATS DEVICES. |
| | IF THE ATS DEVICES CONTAIN A BREAKER FOR NORMAL SIDE |
| | AND A BREAKER FOR EMERGENCY SIDE, PLEASE ADJUST RISER |
| | ACCORDINGLY AND PLEASE BE SURE SPECS/CUT SHEETS |
| | INDICATE THIS. |
| | 110.3, 90.7, 225.31-225.39, 702.11 ETC |
| | |
| | 5) NOTE: PLEASE SEE CIRCLED NOTE # 1 ON RISER ON THE |
| | METER CAN STILL DOES NOT SEEM TO BE AN ACCURATE NOTE. |
| | THE NOTE CALLS FOR THIS METER AS A CT METER ENCLOSURE, |
| | HOWEVER A CT METER ENCLOSURE WOULD NOT INCLUDE A METER |
| | WHICH IS BEING SHOWN ON BOTH RISERS AND PLANS. |
| | PLEASE ADJUST. |
| | IF THIS IS A CT ENCLOSURE, CHANGE RISER TO SHOW THE CT |
| | METER LOCATION. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE GENERATOR SLAB DETAIL ON E-5.2 |
| | IS NOT AS THE SAME AS THE SLAB/FOOTING DETAIL ON |
| | ARCHITECTURAL SHEET 2.0. |
| | PLEASE SEE BUILDING REVIEW COMMENTS. THIS IS NOTED FOR |
| | INFORMATION ONLY AS BOTH OF THESE NEEDS TO COORDINATE. |
| | FBC 106.1.2 |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-10-16 07:59:20 | 2007-10-16 07:59:20 |
| | |
| | IN ELEC FOR REVIEW. |