Plan Review Notes
Plan Review Notes For Permit 07090643
Permit Number 07090643
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-16 09:27:47 
  
 **** DENIED ****
  
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW UNDER
 EXPIRED PERMIT ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SOME NEW COMMENTS BASED ON
 PLANS/DOCUMENTS SUBMITTED.
  
  
 1) NOTE:PLEASE KNOW AS THE PERMIT APPLICATION DATE
 HAS CHANGED.
 PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT CODES ARE
 STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (2002 SHOWN ON PLANS)
  
 IF THIS WAS THE ONLY COMMENT PLANS WOULD HAVE BEEN
 REDLINED, HOWEVER THEY ARE COMING BACK FOR OTHER
 COMMENTS.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORKWAS STILL NOT INCREASED. THE VALUE IS REQUIRED TO
 BE BASED ON ALL LABOR, MATERIALS, EQUIPMENT, DESIGN
 COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 BASED ON ALL THE WORK AS SHOWN ON PLANS ETC THE VALUE
 AS APPLIED IS VERY LOW.
 IF AN APPROPRIATE VALUE IS NOT ADJUSTED, ONE WILL BE
 ASSESSED.
 FBC 108.3
  
 3) NOTE: PLEASE CLARIFY WHY THE GENERATOR SUBMITTALS
 CONTAIN A SEPARATE ELECTRICAL CONTRACTOR ON THE LISTING
 OF COVER SHEET.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 ATS SWITCHES WHICH ARE BEING SHOWN ON THE RISER. PLEASE
 SEE THE NEXT COMMENT FOR DISCONNECTING MEANS REQUIRED.
 FBC 106.1.2.
 NEC 90.7, 110.3.
  
 4) NOTE: PLEASE SEE THE RISER DOES NOT INCLUDE A
 DISCONNECTING MEANS FOR FEEDERS COMING FROM THE
 GENERATOR.
 225.31-225.39.
 (MAY NOT USE BREAKER ON THE GENERATOR AS IT DOES NOT
 MEET 702.11)
 PLEASE INCLUDE DISCONNECT/DISCONNECTS ON THE FEEDERS
 EITHER ON THE LINE SIDE OF GUTTER FROM GENERATOR, OR
 LOAD SIDE OF ATS DEVICES.
 IF THE ATS DEVICES CONTAIN A BREAKER FOR NORMAL SIDE
 AND A BREAKER FOR EMERGENCY SIDE, PLEASE ADJUST RISER
 ACCORDINGLY AND PLEASE BE SURE SPECS/CUT SHEETS
 INDICATE THIS.
 110.3, 90.7, 225.31-225.39, 702.11 ETC
  
 5) NOTE: PLEASE SEE CIRCLED NOTE # 1 ON RISER ON THE
 METER CAN STILL DOES NOT SEEM TO BE AN ACCURATE NOTE.
 THE NOTE CALLS FOR THIS METER AS A CT METER ENCLOSURE,
 HOWEVER A CT METER ENCLOSURE WOULD NOT INCLUDE A METER
 WHICH IS BEING SHOWN ON BOTH RISERS AND PLANS.
 PLEASE ADJUST.
 IF THIS IS A CT ENCLOSURE, CHANGE RISER TO SHOW THE CT
 METER LOCATION.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE GENERATOR SLAB DETAIL ON E-5.2
 IS NOT AS THE SAME AS THE SLAB/FOOTING DETAIL ON
 ARCHITECTURAL SHEET 2.0.
 PLEASE SEE BUILDING REVIEW COMMENTS. THIS IS NOTED FOR
 INFORMATION ONLY AS BOTH OF THESE NEEDS TO COORDINATE.
 FBC 106.1.2
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-16 07:59:202007-10-16 07:59:20
  
 IN ELEC FOR REVIEW.