| Date |
Text |
| 2007-10-20 17:07:19 | |
| | |
| | DENIED |
| | |
| | 1)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $165.85 FOR |
| | INCREASED VALUE THIS AMOUNT IS REQUIRED TO BE PAID |
| | PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. CALC'S ARE NOT SIGNED BY OWNER/AGENT AND |
| | ADDITIONS OR REMODELS REQUIRE A MIN R5 INSULATION AT |
| | EXTERIOR BLOCK WALLS AND MIN R30 IN CEILINGS WITH ATTIC |
| | SPACE PER 13-602.1.C.1.2 & 13-602.1.C.2 FBC FOR WALLS |
| | AND 13-604.1.C.1 & 13-604.1.C.2 FBC FOR CEILINGS |
| | |
| | 5)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER |
| | R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES |
| | |
| | 6)PROVIDE SCHEDULE ON DRAWINGS FOR DOOR AND WINDOW |
| | SIZES/DIMENSIONS, TYPES AND DESIGN PRESSURES |
| | |
| | 7)PROVIDE THE FOLLOWING CORRECTIONS TO SHEET A/1 |
| | CORRECT DIMENSIONS FOR EAST ELEVATION AS THEY ADD UP TO |
| | 26'-1", WINDOW AND DOOR DESIGN PRESSURES,CORRECT |
| | R-VALUES AND 3 BEDROOM WINDOWS SHOW MULLIONS IF SO |
| | PRODUCT APPROVALS WILL BE REQUIRED. PLEASE BE SURE THAT |
| | THEY WILL MEET EMERGENCY EGRESS IF MULLIONS ARE USED. |
| | |
| | 8)PROVIDE PRODUCT APPROVALS FOR SIMPSON |
| | STRAPS/CONNECTORS OR INCLUDE THE CORRECT FLORIDA |
| | PRODUCT APPROVAL #'S ON THE SIMPSON SCHEDULE ON S/1 OR |
| | PROVIDE SIMPSON'S FLORIDA APPROVED INDEX (ON SIMPSON |
| | TIE WEB SITE) AND MARK/HIGHLIGHT THE CONNECTORS THAT |
| | WILL BE USED |
| | |
| | 9)GAF GRAND TIMBERLINE SHINGLES ARE NOT LISTED UNDER |
| | THE FLORIDA APPROVAL #183, REMOVE THE STATE COVER AND |
| | APPROVE THE MIAMI-DADE REPORT THAT HAS BEEN ACCEPTED |
| | FOR LOCAL PRODUCT APPROVAL |
| | |
| | 10)PROVIDE 2 COPIES OF A COMPLETED SHUTTER |
| | INSTALLATION SCHEDULE WITH MOUNTING TYPE FOR THE TOP |
| | AND BOTTOM, PANEL ORIENTATION (HORZ ORVERT), FASTENER |
| | TYPE ETC. FILLED OUT SEE ATTACHED SCHEDULE EXAMPLE |
| | |
| | 11)PROVIDE SYSTEM THAT WILL BE USED FOR MODIFIED |
| | BITUMEN ROOF FROM THE MANY LISTED IN THE PRODUCT |
| | APPROVAL, ALSO PROVIDE CALCULATIONS FOR THE INCREASED |
| | FASTENERS REQUIRED FOR THE PERIMETER AND CORNER ZONES |
| | PER RAS 117 (SEE LIMITATION #7 ON PAGE 32) |
| | |
| | 12)SUBMIT 2 SIGNED AND SEALED ENGINEERED TRUSS |
| | DRAWINGS THAT COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION THAT HAVE BEEN |
| | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 13)NOTE THAT SCOPE OF WORK DOES NOT COVER REPLACEMENT |
| | OF PLUMBING PIPING AND WAS REVIEW AS ONLY FIXTURE |
| | REPLACEMENT IF PIPING WAS DAMAGED AND REQUIRES ANY WORK |
| | STATE ON THE DRAWINGS AND PROVIDE RISER DIAGRAM FOR |
| | COMPLETE PLUMBING REVIEW |
| | |
| | 14)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |