Plan Review Notes
Plan Review Notes For Permit 07090631
Permit Number 07090631
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-01 09:22:06 
  
 PROVISO
 THE EQUIPMENT GROUND BETWEEN THE METER AND DISCONNECT
 ON THE RISER DIAGRAM CREATES A PARALLEL PATH TO GROUND
 WITH THE NEUTRAL AND MUST BE REMOVED. AN ISOLATED
 NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN FROM THE
 FIRST MEANS OF DISCONNECT. 250.6.