Plan Review Notes
Plan Review Notes For Permit 07090628
Permit Number 07090628
Review Stop G
Sequence Number 2
Notes
Date Text
2008-06-05 09:36:15DENIED;
  
 (ONE COPY OF OLD PLANS WAS NOT SUBMITED)
 OLD COMMENTS 1 AND 2, OK
 NEW COMMENTS;
 1.TYPE OF GAS PIPE USED? I.E. BLACK IRON, GALV. ETC.
 PLEASE LIST ON PLAN.
 2.SIZE ALL PIPE.
 3. PAGE 3 OF 3 " DESIGN PARAMETER" SHOWS INLET PRESSURE
 AT 14 "WC, USING FBC FUEL GAS CODE TABLE 402.4(5) PIPE
 WOULD BE 2 1/2".
 4. A REGULATOR IS CALLED FOR AT GENERATOR, AT 1/2 LB
 REGULATOR IS NOT REQUIRED. IF PRESSURE IS CHANGED
 SUBMIT MANUFACTURE AND MOLEL NUMBER OF REGULATOR TO BE
 USED. THE SHUTOFF VALVE SHOWN ON ISOMETRIC AT GENERATOR
 SHOULD BE UP STREAM OF REGULATOR AND A UNION IS
 REQUIRED BEFORE GENERATOR.
 5. TYPE OF GAS USED NATURAL OR L.P.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695