| 2008-06-13 14:36:20 | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SHOW LOCATION OF PROPOSED FUEL SHUT OFF |
| | IN THE PROXIMITY OF THE MAIN ELECTRICAL SWITCH GEAR. |
| | PLEASE PROVIDE NOTES AND ACTUAL WORDING FOR PROPOSED |
| | SIGNAGE AT THE MAIN ELECTRICAL EQUIPMENT LOCATION AS |
| | WELL AS ANY FIRE COMMAND ROOM, ACTUAL FUEL SHUT OFF |
| | LOCATION AND FIRE ENUNCIATOR LOCATION. ANY SIGNAGE IN |
| | BUILDING WHICH DIRECT EMERGENCY PERSONNEL TO THE |
| | LOCATIONS TO SHUT DOWN POWER ETC IN AN EMERGENCY SHALL |
| | BE STATED ON PLANS AND WILL BE VERIFIED IN FIELD. |
| | |
| | AS STATED IN PART 12 OF TITLE 47 THE TIME FOR BACK UP |
| | ARE REQUIRED TO BE A MINIMUM OF 8HRS. PLEASE SHOW THE |
| | EXISTING BATTERY BACK UP UNITS. |
| | |
| | AS PLANS ARE COMING BACK FOR COMMENTS PLEASE SUPPLY AT |
| | THIS TIME. |
| | |
| | ** AS STATED ON PREVIOUS AS NOT ALL ITEMS ARE SHOWN AS |
| | OF YET THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |