| Notes |
| Date |
Text |
| 2007-11-11 11:32:12 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLEASE SHOW THE LOCATION OF ALL OUTSIDE AIR INTAKES, | | | GRAVITY VENTS AND OPENINGS INTO THE BUILDING AND THEIR | | | RELATED DISTANCE TO THE GENERATOR EXHAUST TO SHOW | | | COMPLIANCE WITH FBC,M 401.5.1 AND FBC,M 501.2. | | | | | | 2. THE AIR SUPPLY FOR THE ENGINE SHALL BE DESIGNED TO | | | MEET AT LEAST THE MINIMUM REQUIREMENTS FOR COMBUSTION, | | | COOLING, AND VENTILATION, AND TO PREVENT FLUE GAS | | | PRODUCTS FROM BEING DRAWN FROM STACKS OR FLUES OF | | | BOILERS OR OTHER COMBUSTION DEVICES. SHOW THE LOCATION | | | OF ANY VENTS OR STACKS ON THE ROOF AND THEIR DISTANCES | | | FROM THE COMBUSTION/VENTILATION AIR INTAKES FOR THE | | | GENERATOR IN ACCORDANCE WITH NFPA 37-02 SEC 4.1.1.2. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|