2007-11-11 11:32:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE SHOW THE LOCATION OF ALL OUTSIDE AIR INTAKES,
 GRAVITY VENTS AND OPENINGS INTO THE BUILDING AND THEIR
 RELATED DISTANCE TO THE GENERATOR EXHAUST TO SHOW
 COMPLIANCE WITH FBC,M 401.5.1 AND FBC,M 501.2.
  
 2. THE AIR SUPPLY FOR THE ENGINE SHALL BE DESIGNED TO
 MEET AT LEAST THE MINIMUM REQUIREMENTS FOR COMBUSTION,
 COOLING, AND VENTILATION, AND TO PREVENT FLUE GAS
 PRODUCTS FROM BEING DRAWN FROM STACKS OR FLUES OF
 BOILERS OR OTHER COMBUSTION DEVICES. SHOW THE LOCATION
 OF ANY VENTS OR STACKS ON THE ROOF AND THEIR DISTANCES
 FROM THE COMBUSTION/VENTILATION AIR INTAKES FOR THE
 GENERATOR IN ACCORDANCE WITH NFPA 37-02 SEC 4.1.1.2.
  