Plan Review Notes
Plan Review Notes For Permit 07090628
Permit Number 07090628
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-22 15:25:521. WRONG INSPECTIONS DEPARTMENT LISTED ON PAGE 1. LISTS
 PALM BEACH COUNTY INSTEAD OF WEST PALM BEACH.
  
 2. ANY INSTALLATION OF EQUIPMENT SHALL NOT INTERFERE
 WITH ANY EXISTING FIRE SAFETY EQUIPMENT LOCATED ON THE
 ROOF OR WITHIN THE BUILDING.
  
 3. NO ROUTING OF ELECTRICAL CONDUITS OR PIPING SHALL
 OCCUR WITHIN ANY REQUIRED STAIRWELL FOR THE BUILDING.
  
 4. WHAT SYSTEMS WILL THE GENERATOR BE PROVIDING STANDBY
 POWER FOR. IF ONLY USED FOR COMMUNICATION PURPOSES, IS
 IT LEGALLY REQUIRED TO HAVE STANDBY FUEL SUPPLIES.
 PLEASE PROVIDE MORE DETAILS.
  
 5. PLEASE EXPLAIN INSTALLATION OF FUEL LINE THROUGH
 EXISTING BALCONIES.
  
 6. PLEASE PROVIDE ALL APPLICABLE LISTINGS FOR THE
 GENERATOR.
  
 7. NO PROPANE STORAGE TANKS ARE ALLOWED TO BE INSTALLED
 ON THE ROOF. IF A SECONDARY FUEL SUPPLY IS NECESSARY IT
 WILL NOT BE ALLOWED TO BE STORED ON THE ROOF.
  
 8. A RISER DIAGRAM OF GAS PIPING SHOULD BE PROVIDED
 ILLUSTRATING THE RUN OF PIPING IN RELATION TO BUILDING
 ELEMENTS TO INCLUDE DOORS, WINDOWS, AND OTHER FEATURES
 OF THE BUILDING.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX