| Plan Review Notes For Permit 07090628 |
| Permit Number |
07090628 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-22 15:25:52 | 1. WRONG INSPECTIONS DEPARTMENT LISTED ON PAGE 1. LISTS | | | PALM BEACH COUNTY INSTEAD OF WEST PALM BEACH. | | | | | | 2. ANY INSTALLATION OF EQUIPMENT SHALL NOT INTERFERE | | | WITH ANY EXISTING FIRE SAFETY EQUIPMENT LOCATED ON THE | | | ROOF OR WITHIN THE BUILDING. | | | | | | 3. NO ROUTING OF ELECTRICAL CONDUITS OR PIPING SHALL | | | OCCUR WITHIN ANY REQUIRED STAIRWELL FOR THE BUILDING. | | | | | | 4. WHAT SYSTEMS WILL THE GENERATOR BE PROVIDING STANDBY | | | POWER FOR. IF ONLY USED FOR COMMUNICATION PURPOSES, IS | | | IT LEGALLY REQUIRED TO HAVE STANDBY FUEL SUPPLIES. | | | PLEASE PROVIDE MORE DETAILS. | | | | | | 5. PLEASE EXPLAIN INSTALLATION OF FUEL LINE THROUGH | | | EXISTING BALCONIES. | | | | | | 6. PLEASE PROVIDE ALL APPLICABLE LISTINGS FOR THE | | | GENERATOR. | | | | | | 7. NO PROPANE STORAGE TANKS ARE ALLOWED TO BE INSTALLED | | | ON THE ROOF. IF A SECONDARY FUEL SUPPLY IS NECESSARY IT | | | WILL NOT BE ALLOWED TO BE STORED ON THE ROOF. | | | | | | 8. A RISER DIAGRAM OF GAS PIPING SHOULD BE PROVIDED | | | ILLUSTRATING THE RUN OF PIPING IN RELATION TO BUILDING | | | ELEMENTS TO INCLUDE DOORS, WINDOWS, AND OTHER FEATURES | | | OF THE BUILDING. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | 804-4709 PHONE | | | 804-4774 FAX |
|