| 2007-10-14 14:23:15 | |
| | ** DENIED** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED. |
| | |
| | 2) NOTE: PLEASE SEE THIS APPEARS BY ALL INFORMATION TO |
| | THIS REVIEWER TO BE A LEGALLY REQUIRED SYSTEM PER FS |
| | 365.172 AND TITLE 47 OF FEDERAL REGULATION CODES WHICH |
| | WOULD REQUIRED A ON-SITE FUEL FOR BACK UP OF THE |
| | GENERATOR PER 701.11B3 AND NFPA-1221 |
| | PLEASE SEE REQUIREMENTS FROM THE FIRE MARSHAL AS A |
| | *ROOF-TOP* LP MAY NOT BE PERMITTED. |
| | |
| | 3) NOTE: PLEASE CLARIFY HOW THE DISCONNECTING MEANS FOR |
| | POWER TO BUILDING IS GROUPED OR IN CLOSE PROXIMITY. |
| | 230.72. |
| | THE *SHUNT-TRIP* KILL SWITCH AS SHOWN DOES NOT MEET THE |
| | REQUIREMENTS OF 230.76, 230.79. |
| | ** A COMPLETE SHUT DOWN OF FUEL SUPPLY WOULD BE |
| | REQUIRED AT A MINIMUM. LOCATION ETC WOULD NEED TO BE |
| | GONE OVER ONCE ALL REVIEWS ARE DONE FROM ALL TRADES. |
| | |
| | 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEET |
| | WHICH CORRELATE WITH PLANS AND PERMIT APPLICATION FOR |
| | GENERATOR. SPECS/CUT SHEETS INDICATE 25 AND 27KW UNIT, |
| | NOT 30. |
| | 90.7, 110.3 |
| | |
| | 5) NOTE: PLEASE PROVIDE LOAD ON THE GENERATOR AND TIME |
| | ON ON-SITE FUEL TO BE DETERMINED.701.5 |
| | |
| | 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK INCLUDING ALL LABOR, MATERIALS AND EQUIPMENT EVEN |
| | IF ANY OF THESE ITEMS ARE SUPPLIED BY THE OWNER. AS GAS |
| | IS APPLIED FOR AT THIS TIME, THIS VALUE SHALL ALSO BE |
| | INCLUDED. |
| | PLEASE KEEP IN MIND AS SCOPE OF MAY CHANGE DUE TO |
| | COMMENTS, THE VALUE MAY ALSO NEED TO BE ADJUSTED. THIS |
| | ALSO INCLUDES VALUE FOR DESIGN FEES (PLANS). FBC 108.3 |
| | |
| | ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR |
| | REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS |
| | SUBMITTED. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |