Plan Review Notes
Plan Review Notes For Permit 07090628
Permit Number 07090628
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-14 14:23:15 
 ** DENIED**
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED.
  
 2) NOTE: PLEASE SEE THIS APPEARS BY ALL INFORMATION TO
 THIS REVIEWER TO BE A LEGALLY REQUIRED SYSTEM PER FS
 365.172 AND TITLE 47 OF FEDERAL REGULATION CODES WHICH
 WOULD REQUIRED A ON-SITE FUEL FOR BACK UP OF THE
 GENERATOR PER 701.11B3 AND NFPA-1221
 PLEASE SEE REQUIREMENTS FROM THE FIRE MARSHAL AS A
 *ROOF-TOP* LP MAY NOT BE PERMITTED.
  
 3) NOTE: PLEASE CLARIFY HOW THE DISCONNECTING MEANS FOR
 POWER TO BUILDING IS GROUPED OR IN CLOSE PROXIMITY.
 230.72.
 THE *SHUNT-TRIP* KILL SWITCH AS SHOWN DOES NOT MEET THE
 REQUIREMENTS OF 230.76, 230.79.
 ** A COMPLETE SHUT DOWN OF FUEL SUPPLY WOULD BE
 REQUIRED AT A MINIMUM. LOCATION ETC WOULD NEED TO BE
 GONE OVER ONCE ALL REVIEWS ARE DONE FROM ALL TRADES.
  
 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEET
 WHICH CORRELATE WITH PLANS AND PERMIT APPLICATION FOR
 GENERATOR. SPECS/CUT SHEETS INDICATE 25 AND 27KW UNIT,
 NOT 30.
 90.7, 110.3
  
 5) NOTE: PLEASE PROVIDE LOAD ON THE GENERATOR AND TIME
 ON ON-SITE FUEL TO BE DETERMINED.701.5
  
 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK INCLUDING ALL LABOR, MATERIALS AND EQUIPMENT EVEN
 IF ANY OF THESE ITEMS ARE SUPPLIED BY THE OWNER. AS GAS
 IS APPLIED FOR AT THIS TIME, THIS VALUE SHALL ALSO BE
 INCLUDED.
 PLEASE KEEP IN MIND AS SCOPE OF MAY CHANGE DUE TO
 COMMENTS, THE VALUE MAY ALSO NEED TO BE ADJUSTED. THIS
 ALSO INCLUDES VALUE FOR DESIGN FEES (PLANS). FBC 108.3
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]