| 2007-11-06 12:11:31 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ALONG |
| | WITH SOME NEW COMMENTS ARE IN NEED OF BEING ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE THE CODES AND NOTES ON PLANS STILL |
| | NEED TO BE CORRECTED. PLEASE SEE FOR EXAMPLE: THERE ARE |
| | STILL CODE NOTES ON PLANS TO THE SOUTH FLORIDA BUILDING |
| | CODE WHICH HAS NOT BEEN IN EFFECT SINCE MARCH 02. |
| | PLEASE SEE THE ELECTRICAL LOADCALCULATIONS ETC. |
| | SHEET E.3 |
| | FBC 106.1.2 |
| | |
| | |
| | 2) NOTE: PLEASE SEE SMOKE DETECTOR NOTES ON PLANS STILL |
| | CALL FOR RESIDENTIAL INSTALLATIONS. |
| | ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS |
| | NOTES AS THESE ARE REFERENCING DWELLING UNIT |
| | REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION. |
| | CALLS FOR ARC FAULT PROTECTION ETC. |
| | PLEASE ADJUST NOTES. |
| | FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND |
| | RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES. |
| | |
| | 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES. PLEASE CORRELATE |
| | CIRCUITING PLANS ALSO. PLEASE SEE ROOMS WHERE |
| | CIRCUITING TO SPECIALTY LIGHTING AND CIRCUIT NUMBER AND |
| | PANEL IS BEING REFLECTED HOWEVER THESE DO NOT CORRELATE |
| | WITH THE SAME ROOMS. |
| | PLEASE SEE FOR EXAMPLE, SWITCH SHOWS A GCA -26, YET THE |
| | SAME ROOM SHOWS GCB 28. THIS IS THE SAME FOR SPA ROOM |
| | #1, #2, ETC. |
| | PLEASE SEE CIRCUITS WHICH REFERENCE TO A GCH PANEL YET |
| | NO GCH PANEL SCHEDULE WAS SUBMITTED. |
| | PLEASE SEE THERE ARE SEVERAL OTHER ELECTRICAL OUTLETS |
| | ON PLANS WHICH CONTAIN NO CIRCUITING. |
| | PLEASE SEE THAT THE PANEL SCHEDULES HAVE ALSO NOT BEEN |
| | REVISED. THE CIRCUITS ARE NOT SHOWN SPECIFIC TO ROOMS |
| | AND AREAS IN WHICH THEY FEED. PLEASE SEE 408.4,240.4, |
| | 310.16. |
| | FBC106.1.2, 106.3.5.1.2, 106.5 ETC. |
| | |
| | |
| | 4) NOTE: LIGHTING CONTROL DEVICES ARE NOT SHOWN FOR ALL |
| | LIGHTING. EXAMPLE : ALTERNATE SPA ROOM. |
| | PLEASE INDICATE LIGHTING CONTROLS PER FBC CHAPTER 13 |
| | FOR NEW LIGHTING CONTROL DEVICES BEING INSTALLED. |
| | PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-101 |
| | PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS |
| | SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE |
| | TABLE. |
| | |
| | PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2 |
| | ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR |
| | *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE |
| | NOT LIGHTING REQUIRED. |
| | PLEASE EXPLAIN WHERE SOME OF THE LIGHTING ALLOWANCE |
| | FIGURES ARE DERIVED. FOR EXAMPLE OFFICE LEVELS NOTED AT |
| | 1.5, WHEN THE CODE STATES MAXIMUM AT 1.1. |
| | PLEASE PLACE A TOTAL ON THE MAXIMUM ALLOWED COMPARED TO |
| | THE MAXIMUM DESIGN. |
| | PLEASE SEE THAT THE TRADE OFFS OF TOTAL SPACE IS |
| | PERMITTED HOWEVER THESE FIGURES NEED TO BE CORRECTED |
| | AND KNOW. |
| | PLEASE SEE 13-415.2 |
| | |
| | 5) NOTE:THIS IS THE SAME NOTE AS PREVIOUS. |
| | PLEASE SEE THE PLANS CALL FOR A STEAM ROOM DISCONNECT |
| | NEXT TO STEAM ROOM HOWEVER THIS DOES NOT SHOW |
| | CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE |
| | COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH |
| | PANELS. |
| | PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN |
| | CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE |
| | PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE |
| | EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT |
| | BEEN ADJUSTED AND COMPLETED. |
| | PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT |
| | INCLUDED? |
| | PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL |
| | SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE |
| | CURRENT CODES. |
| | PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND |
| | COMPLETED UPDATED LOAD CALCULATIONS FOR ALL |
| | ELECTRICAL. |
| | PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4 |
| | ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE:THIS IS THE SAME AS PREVIOUS REVIEW. THE |
| | CANDELA LEVELS WERE ADDED HOWEVER NOT HORN LEVELS WHERE |
| | STATED FOR ADA. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE |
| | THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA |
| | REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN |
| | A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW |
| | LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC |
| | ADA. |
| | . |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. |
| | FBC 106.3.5.1.2, 106.1.2 ETC |
| | ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL |
| | AND/OR BUILDING REVIEWER MAY FOLLOW. |
| | |
| | 7) NOTE: PLEASE PROVIDE NOTES ON PLANS PER |
| | 13-413.1.ABC.1.2 AND .2.2 |
| | PLEASE SEE THE FBC FOR ACTUAL WORDING REQUIRED ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |