| 2007-10-04 08:21:04 | DENIED; |
| | 1. PAGE A.0 APLIICABLE CODES, PEASE ADD FLORIDA |
| | BUILDING CODE PLUMBING 2004/2006 SUPPLEMENTS. |
| | 2. PAGE A.1 FLOOR PLAN DOES NOT MATCH P.1 FLOOR PLAN. |
| | A.1 IS MISSING 1 LAV AND URINAL. |
| | 3. PLEASE MARK ON PLANS MENS AND WOMANS LOUNGE ON PLANS |
| | . ( THE FOLLOWING COMMENTS WILL ADDRESS LOUNGE "A" AS |
| | MENS LOUNGE AND LOUNGE "B" AS WOMANS LOUNGE.) |
| | 4.WOMANS LOUNGE TOILETS REQUIRES A MINIMUM OF 21" FROM |
| | THE FRONT OF TOILET TO THE WALL. SECTION 405.3.1. |
| | 5.A HANDICAP DRINKING FOUNTAIN IS REQUIRED TO MEET |
| | MINIMUM REQUIRED PLUMBING FIXTURES SEE TABLE 403.1. D/F |
| | SHALL COMPLY WITH FBC BUILDING CHAPTER 11 |
| | SECTIONS11-4.1.3(10) AND 11-4.15.1 THRU 11-4.15.5. |
| | 6. SUBMIT MANUFACTURE CUT SHEETS FOR STEAM GENERATOR, |
| | LOCATION, AND A DETAIL DRAWING SHOWING WATER SUPPLY AND |
| | LOCATION OF TEMPERATURERELIEF DISCHARGE. SEE |
| | SECTIONS504.6, 504.6.1, 504.7 AND 504.7.2. |
| | 7. WOMANS LOUNGE SHOWS ONLY ONE LAVATORY PIPED TO |
| | SANITARY PEASE CORRECT. |
| | 8. SHOWERS IN WOMANS LOUNGE SHOWS SHOWERS AS EXISTING |
| | AND ALSO THAT ONE TOILET WAS MOVED PLEASE EXPLAIN AND |
| | SHOW ON SANITARY RISER DIAGRAM. |
| | 9. THE FOLLOWING PLUMBING FIXTURES ARE REQUIRED TO MEET |
| | CHAPTER 11 OF THE BUILDING CODE; |
| | ( A) MENS LOUNGE, A LAVATORY IS REQUIRED IN THE |
| | TOILET STALL 11-4.17.3 EXCEPTION. |
| | (B) URINAL TO COMPLY WITH SECTIONS 11-4.18.1 THRU |
| | 11-4.18.4. |
| | (C) MEN AND WOMAN LOUNGE THE SHOWERS ARE REQUIRED |
| | TO MEET SECTIONS11-4.21.1 THRU 11-4.21.8. ( ONLY ONE |
| | SHOWER IN WOMANS LOUNGE MUST COMPLY). |
| | (D) ALL TOILET ROOMS SHALL COMPLY WITH SECTION |
| | 11-4.1.2(6). |
| | (E) BREAK SINK SHALL COMPLY WITH SECTIONS |
| | 11-4.24.1 THRU 11-4.24.7. |
| | (F) ONE OF THE TOILETS IN WOMANS LOUNGE SHALL |
| | MEET THE HANDICAP REQUIREMENTS SEE SECTIONS 11-4.16.1 |
| | THRU 11-4.16.6. |
| | 10. SHOW DETAILS ON PLANS OF ALL HANDICAP FIXTURES |
| | SHOWING ALL REQUIRED MEASUREMENTS. |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 805-6695 |
| | |