| Notes |
| Date |
Text |
| 2007-10-04 16:15:45 | ***DENIED*** | | | | | | 1) PLANS INDICATE SMOKE DETECTORS AS IT APPLIES TO | | | RESIDENTIAL OCCUPANCIES. PLEASE REMOVE INFORMATION THAT | | | IS NOT APPLICABLE TO THIS PROJECT. | | | | | | 2) PLANS ARE SOMEWHAT CONFUSING REGARDING EXITING. | | | PLEASE PROVIDE A CLEAR ILLUSTRATION AND COMMON PATH OF | | | TRAVEL OF REQUIRED MEANS OF EGRESS SHOWING WHERE | | | PERSONS EXIT TO. | | | | | | 3) INDICATE THE LOCATIONS OF REQUIRED 2A-10B,C RATED | | | FIRE EXTINGUISHERS THAT SHALL BE LOCATED NOT TO EXCEED | | | 75' TRAVEL DISTANCE. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 6) DOES THE DOOR TO THE STAIRWELL SWING IN THE CORRECT | | | DIRECTION?PLANS INDICATE AN OCCUPANT LOAD OF 100. | | | EXIT DOORS TO SWING IN DIRECTION OF TRAVEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|