| | ** DENIED *** |
| | |
| | 1) NOTE: PLEASE CORRELATE WHERE WORK IS BEING PERFORMED |
| | AS SHEET A-2 INDICATES *ANUSKA* YET TITLE BLOCKS |
| | INDICATE *NUSH SPA*? |
| | PLEASE ADJUST AND COORDINATE. |
| | FBC 106.1.2, 110.1.2 |
| | FAC 61G1-16.004 |
| | |
| | 2) NOTE: PLEASE SEE THE COVER SHEET DOES REFLECT THE |
| | RELEVANT CODES WHICH ARE TO BE PART OF PROJECT AND |
| | DESIGNS HOWEVER THERE ARE SEVERAL COMMENTS AND NOTES ON |
| | PLANS WHICH REFERENCE CODES WHICH ARE NO LONGER IN |
| | EFFECT. PLEASE SEE SOME OF THESE IN FACT GO BACK TO |
| | SOME 1996 CODES. |
| | PLEASE SEE EXAMPLES ON ELECTRICAL NOTES: |
| | #3 WHICH STATES THE SFBC, SOUTH FLORIDA BUILDING CODE. |
| | # 10 AND #15 WHICH REFLECTS CODE FROM THE 1996 NEC. |
| | |
| | SMOKE DETECTOR NOTES #4 WHICH GIVES CODE SECTIONS FROM |
| | THE 1996 NFPA-72. |
| | |
| | ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS |
| | NOTES AS THESE ARE REFERENCING DWELLING UNIT |
| | REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION. |
| | CALLS FOR ARC FAULT PROTECTION ETC. |
| | PLEASE ADJUST NOTES. |
| | FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND |
| | RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES. |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY INDICATE A |
| | NEW ELECTRICAL PANEL HOWEVER NO ELECTRICAL RISER WAS |
| | SUBMITTED SHOWING THIS NEW PANEL.?? PLEASE ALSO SEE |
| | NONE OF THE EXISTING PANELS LIST ANY OVER CURRENT |
| | PROTECTION FOR THIS NEW PANEL WHICH IS NOTED AND SHOWN |
| | ON E-2 NEXT TO EXISTING PANELS. |
| | PLEASE COORDINATE AS E-1 DOES NOT INDICATE ANY NEW |
| | PANEL? |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 215.5, 310.16, 240.4, 408.4 ETC |
| | |
| | 4) NOTE: PLEASE INDICATE LIGHTING CONTROLS PER FBC |
| | CHAPTER 13 FOR NEW LIGHTING CONTROL DEVICES BEING |
| | INSTALLED. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND |
| | .1.3. |
| | PLEASE SEE 13-101 |
| | PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS |
| | SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE |
| | TABLE. |
| | |
| | PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2 |
| | ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR |
| | *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE |
| | NOT LIGHTING REQUIRED. |
| | PLEASE LABEL ALL LIGHTING FIXTURES AS SHOWN ON PLANS |
| | AND CORRELATE WITH A FIXTURE LEGEND TO BE |
| | SHOWN/SUBMITTED. THE SAME FIXTURE INFORMATION AS LISTED |
| | IN THE LPC TABLE CAN BE USED HOWEVER EACH WOULD CONTAIN |
| | A DESIGNATION. PLEASE KNOW AT THIS TIME THERE SEEMS TO |
| | BE SOME COORDINATION NEED FOR FIXTURE TYPES AND COUNTS |
| | FOR AREAS. PLEASE SEE POS AREA FOR EXAMPLE. |
| | PLEASE ADJUST NOTE. |
| | **PLEASE CALL TO GO OVER. |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS CALL FOR A STEAM ROOM |
| | DISCONNECT NEXT TO STEAM ROOM HOWEVER THIS DOES NOT |
| | SHOW CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE |
| | COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH |
| | PANELS. |
| | PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN |
| | CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE |
| | PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE |
| | EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT |
| | BEEN ADJUSTED AND COMPLETED. |
| | PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT |
| | INCLUDED? |
| | PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL |
| | SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE |
| | CURRENT CODES. |
| | PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND |
| | COMPLETED UPDATED LOAD CALCULATIONS FOR ALL |
| | ELECTRICAL. |
| | PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4 |
| | ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN |
| | A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW |
| | LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC |
| | ADA. |
| | . |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. |
| | FBC 106.3.5.1.2, 106.1.2 ETC |
| | ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL |
| | AND/OR BUILDING REVIEWER MAY FOLLOW. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN ON |
| | PLANS AT THIS TIME, THERE VERY WELL MAY BE NEW COMMENTS |
| | ON THE FOLLOWING REVIEW. REVIEW NOTES CAN ONLY BE GIVEN |
| | FOR PLANS/DOCUMENTS AS SUBMITTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |