Plan Review Notes
Plan Review Notes For Permit 07090592
Permit Number 07090592
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-27 09:45:40 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY. IF THE ARCHITECTS TITLE BLOCK IS
 ON THE PLAN THE ARCITECT MUST SIGN AND SEAL SAME.
  
 3} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE
 FOR RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3
 FBC AS AMENDED
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]