| 2007-10-05 18:56:49 | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT:07090562 |
| | ADD: 2600 N. FLAGLER DR. #710 |
| | CONT: K.L. BREEN BLDRS INC. |
| | TEL: (561) 856-0232 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006/2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED 10/5/07 |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO |
| | INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISHES AND DESIGN FEES. OUR VALUATION |
| | REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST |
| | ANALYSIS SERVICES. |
| | |
| | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | . ------------------------------------- |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | |
| | 5)WPB AMENDMENTS 106.1.3 CONSTRUCTION DOCUMENTS SHALL |
| | BE DIMENSIONED AND DRAWN TO MINIMUM 1/8 INCH SCALE. THE |
| | DRAWINGS SUBMITTED DOES NOT SHOW CLEARLY THE PROPOSED |
| | WORK INDICATED ON THE APPLICATION. SUBMIT AN EXISTING |
| | FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING ALL |
| | CHANGES TO PROVIDE CONFORMITY TO RECORD RETENTION |
| | PROGRAM. SUBMIT DRAFTSMAN QUALITY DRAWINGS WITH A WALL |
| | LEGEND OF EACH TYPE OF WALL TO BE CONSTRUCTED OR DEMO. |
| | |
| | 6)PER FLORIDA STATUTES 481.229 EXEMPTION FROM |
| | ARCHITECTURAL LICENSURE ONLY APPLIES TO 1FAMILY AND 2 |
| | FAMILY RESIDENCES (R3) NOT MULTI FAMILY (R2) OR |
| | BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE |
| | REQUIRED TO BE DRAWN BY A LICENSED DESIGN |
| | PROFESSIONAL. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |