| 2007-09-20 14:59:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION |
| | INSTRUCTIONS THAT WERE SUBMITTED FOR THE COOLER, |
| | EVAPORATOR, AND CONDENSER UNIT ARE DIFFICULT TO READ. |
| | PLEASE SUBMIT CLEARER COPY'S. CONSTRUCTION DOCUMENTS |
| | SHALL BE OF SUFFICIENT CLARITY, SEE F.B.C. 106.1.1. |
| | |
| | 2) PLEASE SUBMIT PRODUCT APPROVAL OR AN N.O.A. FOR |
| | PER-ENGINEERED CONDENSER STANDS, SEE F.S. 553.842(1) |
| | AND F.A.C. RULE 9B-72, 9B-72.005, AND F.A.C. |
| | 9B-72.010(31)(G). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |