2007-09-20 14:59:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS THAT WERE SUBMITTED FOR THE COOLER,
 EVAPORATOR, AND CONDENSER UNIT ARE DIFFICULT TO READ.
 PLEASE SUBMIT CLEARER COPY'S. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY, SEE F.B.C. 106.1.1.
  
 2) PLEASE SUBMIT PRODUCT APPROVAL OR AN N.O.A. FOR
 PER-ENGINEERED CONDENSER STANDS, SEE F.S. 553.842(1)
 AND F.A.C. RULE 9B-72, 9B-72.005, AND F.A.C.
 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]