| 2008-11-24 11:26:37 | ** TEMPORARY FAILED STATUS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED SHEETS E-4 AND E-6 |
| | NEED COORDINATION. PLEASE SEE THE EXTERIOR FIXTURES |
| | SUBMITTED AND SHOWN ON THE PHOTO-METRICS ACTUALLY DO |
| | NOT INCLUDE MANY FIXTURES WHICH DO CONTRIBUTE TO THE |
| | LIGHTING LEVELS. |
| | PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS DO NOT |
| | INCLUDE ALL EXTERIOR FIXTURES. A CALLED WAS PLACED TO |
| | THE ELECTRICAL ENGINEER AND LEAD DESIGNER ON PROJECT. |
| | SHEETS E-4 AND E-6 WILL BE REVISED AT A LATER DATE |
| | HOWEVER THE ENERGY CALCULATIONS WILL NEED TO BE REVISED |
| | AT THIS TIME BEFORE PERMIT ISSUANCE. |
| | 13-415.2.ABC.1.3. |
| | |
| | 2) NOTE: PLEASE SEE THE 2ND SET AS THE PLANS ARE NOT |
| | COMPLETE. SHEETS FA1 AND FA2 ARE MISSING FROM ONE SETS. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |