| 2008-08-27 11:25:12 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | PLAN REVIEW ONLY |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | |
| | ***********NEW COMMENTS*********** |
| | |
| | NEW PLUMBING SHEETS SUBMITTED |
| | |
| | 1B. SHT P-2 SANITARY RISER ISOMETRIC DOES NOT REFLECT |
| | THE FLOOR PLAN. STACK WITH DOUBLE LAV'S P-3 SHOWS A |
| | TRAP TO THE STORAGE ROOM ON THE FLOOR PLAN THAT IS NOT |
| | ON THE RISER DIAGRAM.--THE FLOOR PLAN SHOWS A FLOOR |
| | DRAIN IN THE STORAGE AREA THAT CONNECTS UPSTREAM OF THE |
| | URINALS IN THE MEN'S ROOM 116 THAT IS NOT SHOWN ON THE |
| | RISER DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1 & |
| | 704.--FLOOR DRAIN UPSTREAM OF THE URINALS APPEARS |
| | TO EXCEED THE MAXIMUM DISTANCE FROM THE VENT PER TABLE |
| | 906.1. |
| | |
| | 2B. SHT P-2 DOMESTIC WATER PIPING ISOMETRIC DOES NOT |
| | REFLECT THE FLOOR PLAN NOR DOES IT REFLECT THE PLUMBING |
| | FIXTURE SCHEDULE SHOWN ON SHT P-3. RISER SHOWS A |
| | FIXTURE P-9 DOWNSTREAM OF FIXTURE P-7 IN THE STORAGE |
| | (117) ROOM. THIS IS NOT SHOWN ON THE FLOOR PLAN NOR ON |
| | THE FIXTURE SCHEDULE. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 604. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| | SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |