| 2008-09-05 16:53:09 | BUILDING PLAN REVIEW |
| | PERMIT: 07090553 |
| | ADD: 6255 N. JOG ROAD |
| | CONT: WEST CONSTRUCTION INC. |
| | TEL: (561)588-2027 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 9-5-08 |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1) OK |
| | 2) OK |
| | |
| | RESPONSE NOTED: HOWEVER; THIS INFORMATION IS STILL |
| | REQUIRED. |
| | 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PLEASE |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: (A) ROLL-UP DOORS (B) SHUTTERS |
| | (C) WINDOWS (D) INSULATED METAL ROOF PANELS (E) METAL |
| | WALL PANELS (F ) HOLLOW METAL DOORS (G) IMPACT GLASS |
| | DOOR (H) ALUMINUM LOUVERS 106.3.3* PRODUCT PPROVALS- |
| | 2004 THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | RESPONSE NOTED: HOWEVER; THIS INFORMATION IS STILL |
| | REQUIRED. |
| | 4) SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | 1. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT. |
| | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | 3. ON THE PRODUCT APPROVAL, MARK WHICH DETAILS APPLY TO |
| | THIS JOB. PLEASE USE INK RATHER THAN A HIGHLIGHTER. SEE |
| | ADDITIONAL INFORMATION IN PACKAGE. |
| | |
| | RESPONSE NOTED: HOWEVER; THIS INFORMATION IS STILL |
| | REQUIRED. |
| | 5) ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | ____ 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION, SEE ATTACHED POLICY: MEAN ROOF HEIGHT/ |
| | ROOF PITCH / ROOF DECK TYPE / AREA OF EACH ROOF TYPE |
| | ____2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE EVALUATION REPORT SUBMITTED, |
| | FAC9B72. WWW.FLORIDABUILDING.ORG |
| | ____3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY |
| | YOU ARE USING. ALSO INDICATE WHICH FASTENER IF THE |
| | OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| | ____5) FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | ___ 6) SEE PRODUCT LIMITATION #7. CALCULATIONS PREPARED |
| | BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | |
| | 6) OK |
| | 7) OK |
| | 8) OK |
| | 9) OK |
| | 10) OK |
| | |
| | PROVISOR: PRIOR TO INSTALLATION. |
| | 11) PROVIDE THE SHOP DRAWINGS WHICH SHALL INCLUDE ALL |
| | ROOFING/ JOIST / ALUMINUM LADDER WITH PLATFORM AND |
| | STRUCTURAL DETAILS ETC. FOR THE BUILDING AS STATED ON |
| | SHEET S-1, S-2 AND S-5. THE DRAWINGS SHALL BE REVIEWED |
| | AND APPROVED BY THE DESIGNER OF RECORD. SHEET S-7 MAKES |
| | REFERENCE TO SEE NOTE #6 WHICH IN NOT ON THE SHEET. |
| | DETAIL #9 ON SHEET S-7 REQUIRES THE ENGINEERED DESIGN |
| | FOR THE OVERHANG. |
| | |
| | 12) OK |
| | |
| | NEW: (A) INDICATE THE R-VALUE FOR THE FOAM INSULATION |
| | IN THE CMU EXTERIOR WALLS. |
| | |
| | (B) THE DRAWINGS FROM NUCOR BUILDING SYSTEMS SHALL |
| | CONTAIN THE ORIGINAL SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER. THE SIGNATURE ON THE SHEETS IS A PHOTO-COPY |
| | SIGNATURE. ALL DOCUMENTS BEING FILED FOR PUBLIC RECORD |
| | SHALL CONTAIN THE ORIGINAL SIGNATURE OF THE PERSON WHO |
| | RESPONSIBLE FOR THE DOCUMENT. A PROFESSIONAL ENGINEER |
| | SHALL SIGN HIS NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS AND OTHER |
| | DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT AND |
| | BEING FILED FOR PUBLIC RECORD. FAC 61G15-23.002 AND |
| | FLORIDA STATUTES 471 ALSO SEE FBC 106.1. NOTE: A COVER |
| | OR INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE |
| | USED AND THAT SHEET MUST BE SIGNED, SEALED AND DATED BY |
| | THOSE PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF |
| | THE PRODUCTION AND PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION, AND IF PRACTICING TROUGH A |
| | DULY AUTHORIZED ENGINEERING BUSINESS, THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS SHALL BE INDICATED ON THE SHEET |
| | WITH SUFFICIENT INFORMATION ON THE COVER SHEET OR INDEX |
| | SO THAT THE USER WILL BE AWARE OF EACH PORTION OF THE |
| | DOCUMENT. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |
| | |