| 2008-05-28 16:25:50 | REVIEW #: 2ND **1ST REVIEW FOR PERMIT** |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. OK EXCEPT: PRODUCT APPROVALS SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL IN ACCORDANCE |
| | WITH FBCB 106.3.3. |
| | |
| | 2 THROUGH 9: OK |
| | |
| | 10. ENERGY CALCULATIONS: ON THE CERTIFICATIONS PAGE OF |
| | THE COMPLIANCE FORM, THE BUILDING SHELL AND |
| | ELECTRICAL/LIGHTING DESIGNERS HAVE NOT CERTIFIED |
| | COMPLIANCE WITH THE ENERGY CODE. DESIGN PROFESSIONALS |
| | RESPONSIBLE UNDER FLORIDA LAW FOR THE DESIGN OF |
| | LIGHTING, ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS |
| | AND THE BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF |
| | THOSE BUILDING SYSTEMS WITH THE CODE BY SIGNING AND |
| | PROVIDING THEIR PROFESSIONAL REGISTRATION NUMBER ON THE |
| | ENERGY CODE FORM PROVIDED AS PART OF THE PLANS AND |
| | SPECIFICATIONS TO THE BUILDING DEPARTMENT, OR: |
| | TYPED NAMES AND REGISTRATION NUMBERS MAY BE PROVIDED IN |
| | LIEU OF A SIGNATURE WHERE ALL RELEVANT INFORMATION HAS |
| | BEEN INCLUDED ON SIGNED AND SEALED PLANS IN ACCORDANCE |
| | WITH FBCB 13-103.1.1.1. SHOW COMPLIANCE BY PROVIDING |
| | ONE OF THE TWO REQUIREMENTS LISTED ABOVE. |
| | |
| | THE FOLLOWING ARE EXAMPLES OF AREAS IN THE INPUT DATA |
| | REPORT (IDR) WHICH DO NOT CORRESPOND WITH THE SYSTEMS |
| | AND ASSEMBLIES SHOWN ON PLANS. THIS IS NOT AN |
| | EXHAUSTIVE LIST. PLEASE VERIFY ALL VALUES TO ENSURE |
| | THEY CORRESPOND WITH PLANS AND RESUBMIT. |
| | |
| | A) A/C SYSTEM #3 AND RELATED ENVELOPE COMPONENTS ARE |
| | NOT INCLUDED IN THE IDR OR SYSTEM SIZING SUMMARY. |
| | PLEASE CORRECT AND RESUBMIT. |
| | |
| | B) EXTERIOR BLOCK WALL (P-2 PARTITION DETAIL PG A-10) |
| | DOES NOT CALL FOR ANY INSULATION. THE IDR IS CALLING |
| | FOR 1 INCH INSULATION AT THESE WALLS. |
| | |
| | C) THERE ARE NO DOORS INCLUDED IN THE IDR. |
| | |
| | 11. SEE COMMENT (A) ABOVE. |
| | |
| | 12 AND 13: OK |
| | |
| | NEW: THE MECHANICAL PAGES, WHILE SIGNED AND SEALED BY |
| | JOSE M. MARTINEZ, HAVE THE PRINTED NAME AND LICENSE |
| | NUMBER OF PAUL F. HILLERS DIRECTLY BELOW THE SIGNATURE |
| | AND SEAL OF MR. MARTINEZ. AS THE PRINTED NAME AND |
| | LICENSE NUMBER OF MR. MARTINEZ APPEARS IN THE TITLE |
| | BLOCKS ON THE SAME PAGES, MR. HILLER?S NAME CAN BE |
| | STRUCK FROM THE PLANS AND THE PLANS WILL BE COMPLIANT. |
| | |
| | NOTE: ASIDE FROM THE ABOVE LISTED COMMENTS, THE |
| | MECHANICAL PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE |
| | AND STAMPED. REVIEW WILL REMAIN IN FAILED STATUS |
| | PENDING SUCCESSFUL REVIEW OF ENERGY CALCULATIONS BY ALL |
| | AFFECTED TRADES. |
| | |