| 2008-06-05 15:42:07 | BUILDING PLAN REVIEW |
| | PERMIT: 07090553 |
| | ADD: 6255 N. JOG ROAD |
| | CONT: WEST CONSTRUCTION INC. |
| | TEL: (561)588-2027 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 6-3-08 |
| | REVIEW: 2ST |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) SHEET LS-1 INDICATES THE OCCUPANCY AS A MIXED |
| | OCCUPANCY WITH A S-1 MEDIUM HAZARD SECTION. THERE IS NO |
| | MEDIUM HAZARD MENTION IN THE CODE, SO PLEASE CHANGE THE |
| | INFORMATION ON THE PLANS TO REFLECT THE CORRECT TYPE OF |
| | OCCUPANCY; SEE FBC 311 FOR ADDITIONAL INFORMATION. |
| | PROVIDE THE MSDS INFORMATION ON ALL TYPES AND QUANTITY |
| | OF MATERIALS WHICH WILL BE STORED OR PLACE IN THIS |
| | AREA. THE GROSS BUILDING AREA HAS THE NUMBER 17,500 X |
| | 3, WHICH TABLE DID THIS NUMBER CAME FROM FOR THE TYPE |
| | VB BUILDING? CLARIFY. PLEASE INDICATE THE FLOOD ZONE |
| | INFORMATION ON THE PLANS. |
| | |
| | 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PLEASE |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: (A) ROLL-UP DOORS (B) SHUTTERS |
| | (C) WINDOWS (D) INSULATED METAL ROOF PANELS (E) METAL |
| | WALL PANELS (F ) HOLLOW METAL DOORS (G) IMPACT GLASS |
| | DOOR 106.3.3* PRODUCT PPROVALS- 2004 THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4) SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | 1. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT. |
| | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | 3. ON THE PRODUCT APPROVAL, MARK WHICH DETAILS APPLY TO |
| | THIS JOB. PLEASE USE INK RATHER THAN A HIGHLIGHTER. SEE |
| | ADDITIONAL INFORMATION IN PACKAGE. |
| | |
| | 5) ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | ____ 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION, SEE ATTACHED POLICY: MEAN ROOF HEIGHT/ |
| | ROOF PITCH / ROOF DECK TYPE / AREA OF EACH ROOF TYPE |
| | ____2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE EVALUATION REPORT SUBMITTED, |
| | FAC9B72. WWW.FLORIDABUILDING.ORG ____3) |
| | FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY YOU ARE |
| | USING. ALSO INDICATE WHICH FASTENER IF THE OPTIONS HAVE |
| | DIFFERENT PRESSURE LIMITATIONS. ____5) FOR THE FLAT |
| | DECK, SPECIFY THE ENHANCED FASTENING FOR CORNER AND |
| | PERIMETER ZONES. |
| | ___ 6) SEE PRODUCT LIMITATION #7. CALCULATIONS PREPARED |
| | BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | 6) FBC 1802. THE SOIL REPORT SUBMITTED BY TIERRA |
| | ENGINEERING NEEDS THE ORIGINAL SEAL, CERTIFICATE OF |
| | AUTHORIZATION NUMBER AND SIGNATURE OF THE PERSON TAKING |
| | RESPONSIBLE FOR THE REPORT. |
| | AN ENGINEER PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND |
| | LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| | OF AUTHORIZATION # ON EACH SHEET PER 61G15-23.002 (2) |
| | FAC |
| | |
| | 7) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED. SHEET A-1 FLOOR PLAN IS MISSING THE |
| | DIMENSIONS FOR ALL THE ROOMS. |
| | |
| | 8) SHEET S-3 DETAIL #2; ON THIS SHEET SHOWS THE |
| | MEZZANINE PRE-STRESSED PRE-CAST CONCRETE @ 5? O.C AND |
| | THE MEZZANINE PLAN SHOWS THEM AT 4? O.C. CLARIFY. |
| | |
| | 9) 1009.11.5 HANDRAILS SHALL RETURN TO A WALL, GUARD OR |
| | THE WALKING SURFACE OR SHALL BE CONTINUOUS TO THE |
| | HANDRAIL OF AN ADJACENT STAIR FLIGHT. WHERE HANDRAILS |
| | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| | EXTEND HORIZONTALLY AT LEAST 12 INCHES BEYOND THE TOP |
| | RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD |
| | BEYOND THE BOTTOM RISER. 11-4.9(2) AT THE BOTTOM, THE |
| | HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE |
| | WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER |
| | OF THE EXTENSION SHALL BE HORIZONTAL SEE FIGURE 19C AND |
| | 19D. SEE SHEETS S-3 / A-6. |
| | |
| | 10) FBC 505.1 THE CLEAR HEIGHT ABOVE AND BELOW THE |
| | MEZZANINE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN 7 |
| | FEET. CLEARLY INDICATE THE HEIGHT BETWEEN THE MEZZANINE |
| | FLOOR AND THE CEILING ABOVE. 110.4.2 STORAGE & FACTORY- |
| | INDUSTRIAL OCCUPANCIES. THE CALCULATIONS FOR THE |
| | MEZZANINE FLOOR LOAD SHALL BE SUBMITTED AND ACCOMPANIED |
| | BY AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING |
| | THE SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS |
| | PER SQ FT. THE COMPUTATIONS & AFFIDAVIT SHALL BE FILED |
| | AS A PERMANENT RECORD OF THE BLDG DEPT. |
| | |
| | 11) PROVIDE THE SHOP DRAWINGS WHICH SHALL INCLUDE ALL |
| | ROOFING/ JOIST / ALUMINUM LADDER WITH PLATFORM AND |
| | STRUCTURAL DETAILS ETC. FOR THE BUILDING AS STATED ON |
| | SHEET S-1, S-2 AND S-5. THE DRAWINGS SHALL BE REVIEWED |
| | AND APPROVED BY THE DESIGNER OF RECORD. SHEET S-7 MAKES |
| | REFERENCE TO SEE NOTE #6 WHICH IN NOT ON THE SHEET. |
| | DETAIL #9 ON SHEET S-7 REQUIRES THE ENGINEERED DESIGN |
| | FOR THE OVERHANG. |
| | |
| | 12) 11-4.4.2 HEAD ROOM. WALKS, HALLS, CORRIDORS, |
| | PASSAGEWAYS, AISLES OR OTHER CIRCULATION SPACES SHALL |
| | HAVE 80 INCHES MINIMUM CLEAR HEAD ROOM (SEE FIGURE |
| | 8(A). IF VERTICAL CLEARANCE OF AN AREA ADJOINING AN |
| | ACCESSIBLE ROUTE IS REDUCED TO LESS THAN 80 IN. |
| | (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR |
| | VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED. (SEE |
| | FIGURE 8(C-1). |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |