| 2007-11-01 10:57:58 | *****DENIED***** |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 03.THE PROPOSED FIRE HYDRANTS SHALL BE INSTALLED, |
| | COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK. |
| | ADD TO HYDRANT INFORMATION, SHEET C-5. |
| | |
| | 04.LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS |
| | TO FIRE PROTECTION EQUIPMENT AND DEVICES. |
| | |
| | 05.ON THE LIFE SAFETY SHEET (LS-1) IN THE OCCUPANT |
| | LOAD REFERENCE,THE OCCUPANT LOAD OF 81 LISTED DOES |
| | NOT CORRELATE WITH 71 AS COMPUTED BY THIS WRITER. |
| | |
| | 06.SPECIFY THE WALL AND CEILING FINISH MATERIALS FOR |
| | EXITS, EXIT AISLE CORRIDORS, AND OTHER SPACES IN TERMS |
| | OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 07.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| | NUMERICAL ADDRESS ON THE BUILDING.AS PER WEST PALM |
| | BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN |
| | HEIGHT AND NO LESS THAN 1" IN WIDTH.PLEASE BE ADVISED |
| | THAT THE INSTALLATION OF HURRICANE SHUTTERS SHALL NOT |
| | OBSCURE OR BLOCK VISIBILITY OF THE ADDRESS NUMBERS. |
| | |
| | 08.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE |
| | LOCATION OF THE KNOX BOX.FOR APPLICATIONS, CONTACT |
| | WEST PALM BEACH FIRE PREVENTION BUREAU AT |
| | 561-804-4724. |
| | |
| | 09.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR |
| | HANDRAILS/GUARD RAILS. |
| | |
| | 10.ON SHEET A-9 DOOR SCHEDULE NOTE #1 IS UNCLEAR AND |
| | INCORRECT.CLARIFY BY CHAPTER AND SECTION AS PER |
| | REFERENCING NFPA 101- 2003 EDITION. |
| | |
| | 11.SHOW THE LOCATION OF THE FIRE DEPARTMENT |
| | CONNECTION (FDC).THE FDC SHALL BE EQUIPPED WITH KNOX |
| | LOCKING CAPS.FOR APPLICATIONS, CONTACT WEST PALM |
| | BEACH FIRE PREVENTION BUREAU AT 561-804-4724. |
| | |
| | 12.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE |
| | REQUIRED ON THE FIRE LINE BACKFLOW DEVICE. |
| | |
| | 13.ON SHEET E-6, THERE ARE TWO EMERGENCY LIGHTS |
| | ILLUSTRATED ON THE SOUTH WALL OF THE WORKSHOP BUT ONLY |
| | ONE ILLUSTRATED ON SHEETS LS-1 AND A-2;PLEASE |
| | CORRELATE THE PLAN SHEETS TO REFLECT SAME LOCATION |
| | AND/OR NUMBER OF DEVICES. |
| | |
| | 14.ON SHEET E-6 AND LS-1 THERE IS AN EXIT LIGHT |
| | ILLUSTARATED IN THE OFFICE AREA HALLWAY BUT IS NOT |
| | SHOWN ON SHEET A-2;PLEASE CORRELATE THE PLAN SHEETS |
| | TO REFLECT SAME LOCATION AND/OR NUMBER OF DEVICES. |
| | |
| | 15.ON SHEET FA-1, DELETE REFERENCE IN NOTE #3 TO THE |
| | PALM BEACH COUNTY CODE. |
| | |
| | 16.ON SHEET FA-1, AMEND THE FIRE ALARM SEQUENCE OF |
| | OPERATIONS TO REFLECT THAT DUCT SMOKE DETECTORS |
| | INITIATE A GENERAL FIRE ALARM INSTEAD OF A SUPERVISORY |
| | ALARM. |
| | |
| | 17.THE NUMBER OF DEVICES ILLUSTRATED FOR ROOM 108 ON |
| | SHEET FA-2 DOES NOT CORRELATE WITH THE FIRE ALARM RISER |
| | SHOWN ON THE FA-3 SHEET. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| | ADDRESSED |
| | |
| | |