| 2007-10-15 16:11:29 | **** DENIED **** |
| | |
| | |
| | ** PLAN REVIEW |
| | MAINTENANCE BUILDING |
| | SOLID WASTE AUTHORITY |
| | |
| | 1) NOTE: PLEASE KNOW THE PROJECT HAS ONLY BEEN |
| | SUBMITTED FOR *PLAN REVIEW* ONLY AND HAS NOT BEEN |
| | SUBMITTED FOR PERMIT APPLICATION. |
| | PLEASE KNOW ONCE ALL CODE COMMENTS ARE ADDRESSED, PLANS |
| | WILL STILL BE IN A FAILED STATUS UNTIL PERMIT |
| | APPLICATION IS MADE. |
| | ALL VERIFICATION OF LICENSE INFORMATION WILL BE DONE AT |
| | THAT TIME. |
| | |
| | 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| | CODES ARE STATED ON PLANS. |
| | PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER |
| | DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A |
| | MINIMUM. |
| | PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE |
| | REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE |
| | FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS |
| | FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE SOME CODES ON SOME SHEETS ARE NO LONGER |
| | IN EFFECT. FOR EXAMPLE, PLEASE SEE FA-1 WHICH |
| | REFERENCES THE 2000 LS CODE, 2002 NEC IN NOTES 10 AND |
| | 12. |
| | PLEASE ALSO SEE NOTES MENTIONS *PALM BEACH COUNTY*, THE |
| | ACTUAL LOCATION IS IN THE CITY OF WEST PALM BEACH |
| | JURISDICTION. |
| | |
| | FBC 106.1.2, 110.1.2 ETC. |
| | |
| | 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS TO COMPLY |
| | WITH THE CURRENT FBC AS NOTED ABOVE. |
| | PLEASE BE SURE ALL EXTERIOR AND INTERIOR LIGHTING ON |
| | PLANS COORDINATE WITH THE INPUT DATA REPORTS. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415, |
| | 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | AS NO ENERGY CALCULATIONS WERE SUBMITTED NO REVIEW CAN |
| | BE DONE AT THIS TIME. THERE MAY BE NEW COMMENTS ON THE |
| | NEXT REVIEW. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| | .1.4 FOR MISSING LIGHTING CONTROLS REQUIRED. |
| | PLEASE INDICATE TIME SCHEDULING IF TIMER CONTROLLED. |
| | PLEASE INDICATE OVER RIDE DEVICES. |
| | PLEASE INDICATE OVER RIDE MAXIMUM TIMES. |
| | **(PLEASE SEE THE MAXIMUM TIMES FOR OCCUPANCY TYPE |
| | DEVICES ARE 30MINS AND MAXIMUM FOR TIMER OVER RIDE IS |
| | 4HRS) NOTED FOR INFORMATION) |
| | |
| | 5) NOTE: PLEASE CORRELATE ALL LIGHTING CONTROL DEVICES |
| | WITH THE SYMBOL LEGEND. FOR EXAMPLE: PLEASE SEE S WITH |
| | THE LETTER DESIGNATIONS IS NOT ALL ON LEGEND. SEE SX IN |
| | WOMEN'S TOILET, SEE SU IN JAN'S CLOSET. THESE ARE A FEW |
| | AS NOTED. THE COMMENT #4 WILL REQUIRE ADJUSTMENTS |
| | ALSO. |
| | |
| | 6) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR |
| | MINIMUM ADA LEVELS FOR ALL HORN AND STROBE DEVICES. |
| | PLEASE SEE THE PLANS INDICATE ON LEGEND A *XX* FOR |
| | CANDELA LEVELS. PLEASE KNOW THAT ALL LEVELS ARE |
| | REQUIRED. PLEASE SEE THERE ARE SEVERAL LOCATIONS ON |
| | PLANS IN WHICH LESS THAN 75 CD IS BEING SHOWN. |
| | (EXAMPLE: 15, 30) PLEASE SEE .3(4) OF SECTION GIVEN AS |
| | THE MINIMUM LEVEL IS 75 CD. |
| | PLEASE ADJUST. |
| | |
| | 7) NOTE: PLEASE ADJUST ALL CIRCUITING ON PANEL |
| | SCHEDULE(S) AS THE CIRCUITS ARE REQUIRED TO BE SPECIFIC |
| | TO ALL ROOMS AND AREAS IN WHICH THEY FEED. PLEASE KNOW |
| | THE GENERAL USE OF *LIGHTING* AND *RECEPTACLES* NEEDS |
| | TO BE SPECIFIC. |
| | THE ROOMS AND AREAS MAY CONTAIN A NUMERICAL DESIGNATION |
| | IF DESIRED. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| | FROM THE NEC. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2, 110.1.2, 106.1.2 |
| | |
| | 8) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE FOLLOWING ITEMS. |
| | ATS, AND GENERATOR TAP BOX. |
| | ** PLEASE BE AWARE THERE ARE TAP BOXES ON THE MARKER |
| | WHICH THIS AHJ HAS SEEN WHICH ARE NOT LISTED FOR USE, |
| | AND WET/OUTDOORLOCATIONS WHEN CONNECTIONS ARE MADE. |
| | 90.7, 110.3 |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE CLARIFY GENERATOR, AS THE TRANSFER |
| | SWITCH BEING INSTALLED IS AN AUTOMATIC DEVICE WHICH |
| | LENDS TO A PERMANENTLY INSTALLED GENERATOR HOWEVER |
| | COULD NOT LOCATE THIS UNIT ON PLANS. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 10) NOTE: PLEASE CLARIFY THE MAIN AS SHOWN ON RISER |
| | AHEAD OF THE ATS. THIS DISCONNECT SEEMS TO INDICATE A |
| | *SHUNT TRIP* PUSH BUTTON OF SOME TYPE FROM A GLASS |
| | BREAK. DOES THIS MAIN STILL CONTAIN A MANUAL MEANS OF |
| | DISCONNECT RATED FOR THE LOAD SERVED PER 230.76 AND |
| | 230.79? |
| | 110.3, 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 11) NOTE: PLEASE CLARIFY THE MAIN CIRCUIT BREAKER FOR |
| | PANEL DP. THE RISER CONTAINS A NOTE WHICH MENTIONS THIS |
| | IS NOT TO BE SERVICE ENTRANCE RATED? |
| | AS THE INSTALLATION OF THE GENERATOR IS NOT CLEAR AT |
| | THIS TIME, PLEASE BE SURE TO SEE 225.31-225.39 ALONG |
| | WITH 702.11 AS THE DISCONNECTING MEANS FOR THE FEEDERS |
| | COMING FROM A GENERATOR NEEDS TO MEET THE SECTIONS AS |
| | NOTED ABOVE. |
| | PLEASE ALSO CLARIFY THE NOTE ON THE PANEL DP WHICH |
| | MENTIONS THIS EQUIPMENT IS: * 800A, 277/480V, |
| | *4P*,,,,*.IT IS UNCLEAR WHAT THE 4P IS. IS THE |
| | NEUTRAL BEING CONTROLLED BY THIS BREAKER? |
| | PLEASE SUBMIT THE SPECS/CUT SHEET FOR THIS EQUIPMENT. |
| | 110.3, 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 12) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE STAIRS |
| | UNDER NORMAL AND EMERGENCY USE. PLEASE SEE NFPA-101 |
| | 7.8.1.3, AND 7.9.2.2 FOR MINIMUM LEVELS OF 10FT CANDLES |
| | UNDER NORMAL AND IS PERMITTED DOWN TO 1FT CANDLE UNDER |
| | EMERGENCY. |
| | FAC 61G15-33.004 |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE THE FOOTING STEEL WHICH IS |
| | REQUIRED TO BE PART OF THE GROUNDING ELECTRODE SYSTEM |
| | COULD NOT BE LOCATED ON RISER/PLANS PER 250.50. |
| | |
| | 14) NOTE: PLEASE INDICATE A DETAIL/SHOW LOCATION OF THE |
| | TRANSFORMER GROUNDING ELECTRODE SYSTEM PER 250.20, |
| | 250.30, AND 250.50 |
| | |
| | 15) NOTE: PLEASE SEE THE ADDRESS IS MISSING ON |
| | PLANS/TITLE BLOCKS PER 61G15-23.002 AND 61G1-16.004. |
| | FBC 110.1.2, 106.1.2, 106.3.5 |
| | PLEASE KNOW THE ADDRESS LOCATION AS APPLIED FOR AT THE |
| | PCN LOCATION PROVIDED ON PLAN REVIEW APPLICATION IS |
| | 6255 N. JOG RD. |
| | THIS IS NOT YET CONFIRMED AND HAS BEEN ROUTED TO THE |
| | ADDRESSING REVIEWER FOR VERIFICATION FOR ACTUAL SITE |
| | ADDRESS CONFIRMATION. |
| | PLEASE DO NOT BASE ADDRESS ON TITLE BLOCKS UNTIL |
| | VERIFIED WITH THE ADDRESSING REVIEWER. |
| | |
| | 16) NOTE: PLEASE KNOW ALL LOW VOLTAGE AS SHOWN ON PLANS |
| | WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. THESE |
| | MAY BE USED FOR REFERENCING HOWEVER WILL BE REQUIRED TO |
| | PULL SEPARATE PERMITS. |
| | THE LV FOR CATV |
| | LV FOR SECURITY IS REQUIRED UNDER SEPARATE LV PERMIT |
| | FROM CATV, PHONE ETC. |
| | ** THIS IS NOTED FOR INFORMATIONAL PURPOSE ONLY AND NO |
| | CORRECTIONS OR ADJUSTMENTS TO PLANS ARE NEEDED. |
| | |
| | 17) NOTE: PLEASE KNOW THE AIC RATINGS SHALL BE SET AND |
| | STATED BY THE ENGINEER OF RECORD. THE AVAILABLE FAULT |
| | CURRENT SHOULD BE DETERMINED AND SIZING OF EQUIPMENT IS |
| | REQUIRED BASED ON THE AVAILABLE FAULT CURRENT. |
| | NOTES ON RISER *KEYED NOTES* MENTIONS THIS IS TO BE |
| | DONE BY THE ELECTRICAL CONTRACTOR AND THE LEVELS ON |
| | PLANS ARE FOR BIDDING PURPOSES ONLY. |
| | PLEASE SEE 110.9 NEC. |
| | FBC 106.1.2, 106.3.5, ETC AS THE RECORD SETS OF PLANS |
| | ARE REQUIRED TOCONTAIN THE ACTUAL INSTALLED AND |
| | SPECIFIED. |
| | |
| | 18) NOTE: PLEASE VERIFY CIRCUITING FOR SITE LIGHTING |
| | AS SHOWN ON E-3 WHICH IS CIRCUITED TO H1-6 AND THIS |
| | SAME CIRCUIT IS FOR SEVERAL WALL LIGHTING FIXTURES ON |
| | BUILDING ON E-6. |
| | PLEASE SEE PANEL SCHEDULE ON E-10 MENTIONS WALL |
| | LIGHTING ONLY. |
| | |
| | 19) NOTE: *** IMPORTANT, AS THERE ARE SEVERAL ITEMS NOT |
| | YET SUBMITTED FOR REVIEW, REVIEW NOTES ABOVE CAN ONLY |
| | BE DONE ON DOCUMENTS AND PLANS SUBMITTED. |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW BASED |
| | ON NEW PLANS, CHANGES ETC WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2007-10-15 13:07:27 | |
| | |
| | IHN ELEC FOR REVIEW. |