| Date |
Text |
| 2007-10-29 11:40:30 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, |
| | WEST PALM BEACH, FLORIDA33401 |
| | TEL:561-805-6713FAX:561-805-6731 |
| | |
| | JAMES JOHNSTON, |
| | BUILDING PLAN EXAMINER II |
| | E-MAIL:JJOHNSTON @WPB.ORG |
| | |
| | |
| | |
| | |
| | BASIC WIND SPEED ? MPH140 |
| | |
| | PERMIT NO 07090553 |
| | PROJECTMAINTENANCE FACILITY SOLID WASTE ADDRESS |
| | 6255 N JOG ROAD |
| | |
| | DATE10/26/07 |
| | |
| | |
| | BUILDINGPLANREVIEW |
| | |
| | FLORIDA BUILDING CODES 2004 |
| | |
| | 1 |
| | PROJECT INFORMATION SHEETLS-1 |
| | FBCBUILDING503 |
| | TYPE OF CONSTRUCTION V - B |
| | THEB OCCUPANCY IS RATED V-B |
| | S-1 OCCUPANCY IS RATEDV-B |
| | COMMENT-PLEASE NOTE ON SHEETLS-1 |
| | |
| | |
| | 1-A |
| | WPB AMENDMENTS TO FBC 2004 EDITION |
| | BASIC WIND SPEED |
| | 117.1 BASIC WIND SPEED. THE CITY OF WEST PALM BEACH |
| | FALLS ENTIRELY IN THE 140 MPH REGION COMMENT-THE |
| | BASIC WIND SPEED IS 140 MPH |
| | PLEASE NOTE ON SHEETLS-1 |
| | |
| | |
| | 1-B |
| | FBCBUILDING1604.5 |
| | WIND IMPORTANCE FACTORII |
| | COMMENT- |
| | PLEASE NOTE ON SHEETLS-1 |
| | |
| | 1-C |
| | FBCBUILDING 1604.5 |
| | WIND EXPOSURE |
| | COMMENT- |
| | PLEASE NOTE ON SHEETLS-1 |
| | |
| | |
| | 2 |
| | FBCBUILDING1802.6SOIL TEST REPORT |
| | THE SOIL CLASSIFICATION AND DESIGN LOAD-BEARING |
| | CAPACITY |
| | SHALL BE SHOWN ON THE CONSTRUCTION DOCUMENT. |
| | WHERE REQUIRED BY THE BUILDING OFFICIAL, A WRITTEN |
| | REPORT |
| | OF THE INVESTIGATION SHALL BE SUBMITTED THAT INCLUDES, |
| | BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION: |
| | COMMENT-PLEASE SUBMIT THE SOIL TEST REPORT FOR THIS |
| | PROJECT |
| | |
| | |
| | 3 |
| | WPB ADMENDMENT109.3.4 TERMITES. BUILDING COMPONENTS |
| | AND BUILDING SURROUNDINGS REQUIRED TO BE PROTECTED FROM |
| | TERMITE DAMAGE IN ACCORDANCE WITH SECTION 1503.6, |
| | SECTION 2304.13 OR SECTION 2304.11.6, SPECIFICALLY |
| | REQUIRED TO BE INSPECTED FOR TERMITES IN ACCORDANCE |
| | WITH SECTION 2114, OR REQUIRED TO HAVE CHEMICAL SOIL |
| | TREATMENT IN ACCORDANCE WITH SECTION 1816 SHALL NOT BE |
| | COVERED OR CONCEALED UNTIL THE RELEASE |
| | FROM THE BUILDING OFFICIAL HAS BEEN RECEIVED COMMENT |
| | PLEASE PROVIDE THIS INFORMATION ON DRAWINGS |
| | |
| | |
| | 4 |
| | FLORIDA STATUE713.13NOTICE OF COMMENCEMENT FILE |
| | NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. IF |
| | THE |
| | WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED WITHIN |
| | 90 |
| | DAYS OF FILING THE NOTICE WILL BECOME NULL AND VOID. |
| | SUBMIT THE NOTICE AT THE TIME OF PERMIT ISSUANCE AND |
| | POST A COPY AT THE JOB SITE BEFORE THE FIRST |
| | INSPECTION. |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | |
| | 5 |
| | FBC BUILDING504.2 AUTOMATIC SPRINKLER SYSTEM |
| | INCREASE. |
| | THIS CHAPTER OF THE CODE ALLOWS THE BUILDING HEIGHT TO |
| | BE INCREASED BY 20? AND THE MAXIMUM NO. OF STORIES |
| | INCREASE BY ONE STORY |
| | COMMENT-FOR YOUR INFORMATION TYPE OF |
| | |
| | |
| | 5-A |
| | FBC BUILDING506.3 AUTOMATIC SPRINKLER SYSTEM |
| | INCREASE |
| | |
| | COMMENT- |
| | AREA INCREASE WITH AUTOMATIC SPRINKLER SYSTEM IS 300 |
| | PERCENT FOR SINGLE STORY BUILDING |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | 6 |
| | PRODUCT APPROVALS REQUIRED |
| | FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 |
| | REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS |
| | SUBMIT TWO COPIES OF EACH APPROVAL |
| | ( 3 COPIES IF A THRESHOLD BUILDING ) WITH FLORIDA |
| | PRODUCT |
| | APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S |
| | SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR |
| | KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH |
| | THE PLANS AND SPECIFICATIONS. |
| | SEE:WEB SITEWWW.FLORIDABUILDING.COM |
| | |
| | ALUMINUM WINDOWS |
| | FIXED GLASS |
| | MULLION TUBES |
| | ALUMINUM OUT -SWING DOORS |
| | HOLLOW METAL DOORS |
| | EXTERIOR GLAZED DOORS |
| | HURRICANE SHUTTERS |
| | LOUVERS,NO REPORT SUBMITTED |
| | ROLL UP DOOR |
| | COMMENT-PLEASE PROVIDE THE FOLLOWING FLORIDA PRODUCT |
| | APPROVALS |
| | |
| | |
| | 7 |
| | FBC BUILDING1609.6 SIMPLIFIED WIND LOAD METHOD. |
| | 1609.1 APPLICATIONS. |
| | BUILDINGS, STRUCTURES AND PARTS THEREOF SHALL BE |
| | DESIGNED |
| | TO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED HEREIN. |
| | |
| | COMMENT-PLEASEPROVIDE THE DESIGN PRESSURE FOR THE |
| | WINDOWS AND DOORS, GARAGE DOORS, LOUVERS, MULLIONS |
| | |
| | |
| | 8 |
| | WPB AMENDMENTS TO FBC 2004 EDITION |
| | 110.4.2 STORAGE AND FACTORY-INDUSTRIAL OCCUPANCIES. IT |
| | SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| | PROPRIETOR OR OCCUPANT OF GROUP S WHERE EXCESSIVE FLOOR |
| | LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| | ARCHITECT OR ENGINEER IN COMPUTING THE SAFE LOAD |
| | CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| | AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| | SAFE ALLOWABLE FLOOR LOAD ON EACH FLOOR IN POUNDS PER |
| | SQUARE FOOT UNIFORMLY DISTRIBUTED |
| | 110.4.3 SIGNS REQUIRED. |
| | COMMENTIN EVERY BUILDING OR PART OF A BUILDING A SAFE |
| | FLOOR LOAD SHALL BE POSTED IN A CONSPICUOUS LOCATION. |
| | THIS SECTION REFERS TO THE MEZZANINE. PLEASE |
| | FURNISH THE SAFE LOAD CAPACITY AND NOT ON PLAN THE |
| | REQUIRED INFORMATION TO BE POSTED AT THE MEZZANINE. |
| | |
| | |
| | 9 |
| | FBC BUILDING 2200 |
| | THE FOLLOWING INFORMATION IS PROVIDED FOR |
| | REVIEW BY THE DESIGNER OF RECORD, THE |
| | SPECIALITY ENGINEER, AND THE PROJECT |
| | ENGINEER |
| | |
| | |
| | 10 |
| | FBC BUILDING2223.5.3 |
| | COMMENT THE MANUFACTURER SHALL DESIGN THE METAL SYSTEM |
| | BUILDING AND/OR COMPONENT SYSTEM IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 16 |
| | METAL BUILDING STRUCTURAL DESIGN, PANEL WALLS INSULATED |
| | PANEL CEILING, PRE-ENGINEERED METAL CANOPY |
| | COMMENT-PLEASE PROVIDE THE SPECIAL ENGINEERING?S |
| | DESIGN AND SPECIFICATIONS FOR THE METAL BUILDING |
| | COMPONENTS |
| | |
| | |
| | 10-A |
| | FBC BUILDING2223.4.1 |
| | COMMENT -THE STRUCTURAL ENGINEER OF RECORD AND/OR THE |
| | ARCHITECTOF RECORD SHALL REQUIRE STRUCTURAL |
| | SUBMITTALS FOR REVIEW |
| | AS AN INDICATION THAT HIS OR HER INTENT HAS BEEN |
| | UNDERSTOOD |
| | AND THAT THE SPECIFIED CRITERIA HAVE BEEN USED. THE |
| | STRUCTURAL SUBMITTALS SHALL BEAR THE IMPRESSED SEAL, |
| | SIGNATURE AND DATE OF THE SPECIALTY ENGINEER WHO |
| | PREPARED THEM. |
| | |
| | 10-B |
| | FBC BUILDING2222.4.8 |
| | METAL SIDING AND ROOF PANELS SHALL BE DESIGNED, WHERE |
| | POSSIBLE, TO BE CONTINUOUS OVER TWO OR MORE SPANS. |
| | COMMENT PLEASESUBMIT THE METAL BUILDING SPECIALTY |
| | ENGINEERING DESIGN FOR PLAN REVIEW COMPLIANCE NOTING |
| | THE INFORMATION PROVIDEDHEREIN |
| | |
| | |
| | 10-C |
| | FBC BUILDING2223.5.1 |
| | COMMENT CALCULATIONS FOR DRIFT AND DEFLECTION OF THE |
| | METAL |
| | SYSTEM BUILDING SHALL BE BY THE SPECIALTY ENGINEER. |
| | |
| | |
| | 10-D |
| | FBC BUILDING2223.8.4 |
| | STRUCTURAL STANDING-SEAM ROOF SHEETS SHALL BE A |
| | MINIMUM |
| | OF 24 GAUGE [0.0239 INCH (.6 MM) NOMINAL] IN THICKNESS |
| | COMMENT FOR YOUR INFORMATION |
| | |
| | 10-E |
| | FBC BUILDING2223.8.5 |
| | DIRECT SCREW ATTACHED ROOF AND WALL SHEETS MAY BE USED |
| | AS |
| | DIAPHRAGMS PROVIDED THE SHEETS ARE A MINIMUM OF 24 |
| | GAUGE |
| | COMMENTFOR YOUR INFORMATION |
| | |
| | 10-F |
| | 2222.4.3 |
| | FBC BUILDINGMETAL SIDING AND ROOF PANELS SHALL BE |
| | NOT |
| | |
| | LESS THAN 24 GAUGE. |
| | COMMENTFOR YOUR INFORMATION |
| | |
| | |
| | 10-G |
| | 2222.4.5 |
| | FBC BUILDINGTHE BENDING STRESS OF METAL SIDING AND |
| | ROOF |
| | PANELS SHALL BE DESIGNED USING A SAFETY FACTOR OF NOT |
| | LESS |
| | THAN 2.5. |
| | COMMENT FOR YOUR INFORMATION |
| | |
| | 11 |
| | FBC BUILDING 1600 LOADS |
| | COMMENT PLEASE VERIFY THE SUSPENDED GYPSUM CEILING |
| | SUPPORTED BY THE METAL ROOF STRUCTURE SYSTEM |
| | COMPONENTS |
| | WILL CARRY THE LOAD IMPOSED BY THIS CEILING SYSTEM. |
| | THIS WILL BE REFLECTED IN THE STRUCTURAL DESIGN BY THE |
| | METAL |
| | BUILDING MANUFACTURER?SSPECIALTY ENGINEER |
| | |
| | |
| | 12 |
| | FBC BUILDING CHAPTER 11 ACCESSIBILITY |
| | 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW |
| | CONSTRUCTION |
| | SHEETC-1COMMENT PLEASE PROVIDE A DETAIL FOR THE |
| | 5? |
| | |
| | WIDE HANDICAP ACCESSIBLE ISLE FROM THE PARKING LOT TO |
| | THE |
| | SIDEWALK WITH A LEVEL CONNECTION |
| | |
| | |
| | 13 |
| | FLORIDA BUILDING CODE BUILDING 1210.2 WALLS. COMMENT |
| | PLEASE NOTE ON PLAN.. WALLS WITHIN 2 FEET OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE |
| | FLOOR |
| | |
| | |
| | 14 |
| | FLORIDA BUILDING CODE BUILDING 713.1 GENERAL - FIRE |
| | RESISTANT JOINT SYSTEM |
| | COMMENTOCCUPANCY SEPARATION WALL. JOINTS |
| | INSTALLED |
| | |
| | IN OR BETWEEN FIRE-RESISTANCE-RATED, WALLS,FLOOR OR |
| | FLOOR/CEILING |
| | ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| | BE |
| | PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | |
| | 15 |
| | FBC BUILDING1207.2AIR-BORNE SOUND. |
| | COMMENTWALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC |
| | OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | |
| | (STC) OF NOT LESS THAN 50 |