| 2008-04-08 07:10:05 | BUILDING PLAN REVIEW |
| | PERMIT: 07090539 |
| | ADD: 5601 CORPORATE WAY #200 |
| | CONT: CLAY KOHLMEYER GEN. CONTR INC. |
| | TEL: (561)694-1214 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: REVISION |
| | ACTION: DENIED |
| | |
| | 1)ALL PLANS AND SPECIFICATIONS SUBMITTED BY AN |
| | ENGINEER BEING FILED FOR PUBLIC RECORD SHALL HAVE THE |
| | ORIGINAL SEAL, SIGNATURE AND DATE ON SUCH INFORMATION. |
| | IF PRACTICING THROUGH A DULY AUTHORIZE ENGINEERING |
| | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME |
| | AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND |
| | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. PHOTO-COPY SEAL, AND SIGNATURES |
| | ARE NOT ACCEPTABLE. |
| | |
| | 2)WPB AMENDMENTS 106.1.3* ONLY THE ENGINEER OF RECORD |
| | CAN ADD INFORMATION TO THE DRAWINGS. NO WHITE-OUT, PEN |
| | OR PENCIL HANDWRITING IS ALLOWED ON THE DRAWINGS. THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, STANDARDS FOR PLANS AND SPECIFICATIONS IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | SOME OF THE INFORMATION ON THE SUBMITTAL IS ILLEGIBLE. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION AND NATURE OF THE WORK |
| | PROPOSED. |
| | |
| | 3)INDICATE HOW THE 2X8 WILL BE ATTACHED TO THE |
| | EXISTING CONCRETE BLOCK WALL. PROVIDE AN ELEVATION |
| | DETAIL DRAWING OF THE EACH WALL WHERE THE SUPPORT ANGLE |
| | HAS TO BE INSTALLED, INCLUDING THE FULL HEIGHT OF THE |
| | WALL. ADDITIONAL INFORMATION IS REQUIRED 106.1.2* |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |