| Plan Review Notes For Permit 07090539 |
| Permit Number |
07090539 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-04 11:50:27 | ** DENIED 2NDREVIEW ** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE | | | STILL IN NEED OF ADDRESSING | | | | | | 1) NOTE: PLEASE SEE NO MAXIMUM TIMES FOR OCCUPANCY TYPE | | | DEVICES NOTED. | | | 13-415.1.ABC.1.2. | | | PLEASE KNOW THE MAXIMUM TIME OF 30MINS COULD HAVE BEEN | | | REDLINED HOWEVER THE COMMENT NUMBER TWO NEEDS TO BE | | | ADDRESSED. THIS INFORMATION CAN BE ADDED AS PLANS NEED | | | CORRECTIONS. | | | | | | 2) NOTE: PLEASE SEE THE ELECTRICAL PANEL IS STILL BEING | | | SHOWN IN THE STORAGE ROOM WHICH IS NOT PERMITTED. | | | PLEASE SEE RESPONSE MENTIONS ROOM WAS NOT LABELED | | | CORRECTLY HOWEVER PLANS HAVE NOT CHANGED. PLEASE SEE | | | POWER ON E-2. | | | PLEASE SEE 408.7, 110.26, AND 240.24 AS THIS IS A FIRE | | | AND LIFE SAFETY ISSUE. | | | PLEASE RELOCATE PANEL. | | | IF ROOM IS AN ELECTRICAL ROOM, NOTES FOR SIGNS FOR NO | | | STORAGE ON DOOR, ETC WILL BE REQUIRED. | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|