Plan Review Notes
Plan Review Notes For Permit 07090539
Permit Number 07090539
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-04 11:50:27** DENIED 2NDREVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING
  
 1) NOTE: PLEASE SEE NO MAXIMUM TIMES FOR OCCUPANCY TYPE
 DEVICES NOTED.
 13-415.1.ABC.1.2.
 PLEASE KNOW THE MAXIMUM TIME OF 30MINS COULD HAVE BEEN
 REDLINED HOWEVER THE COMMENT NUMBER TWO NEEDS TO BE
 ADDRESSED. THIS INFORMATION CAN BE ADDED AS PLANS NEED
 CORRECTIONS.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PANEL IS STILL BEING
 SHOWN IN THE STORAGE ROOM WHICH IS NOT PERMITTED.
 PLEASE SEE RESPONSE MENTIONS ROOM WAS NOT LABELED
 CORRECTLY HOWEVER PLANS HAVE NOT CHANGED. PLEASE SEE
 POWER ON E-2.
 PLEASE SEE 408.7, 110.26, AND 240.24 AS THIS IS A FIRE
 AND LIFE SAFETY ISSUE.
 PLEASE RELOCATE PANEL.
 IF ROOM IS AN ELECTRICAL ROOM, NOTES FOR SIGNS FOR NO
 STORAGE ON DOOR, ETC WILL BE REQUIRED.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  