Plan Review Notes
Plan Review Notes For Permit 07090539
Permit Number 07090539
Review Stop M
Sequence Number 1
Notes
Date Text
2007-11-11 09:44:16REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO LEVEL OF ALTERATION HAS BEEN DECLARED ON PLANS.
 THE DESIGN PROFESSIONAL MUST ELECT ONE OR A COMBINATION
 OF LEVELS OF ALTERATION PURSUANT TO SECTIONS 303, 304
 AND 305 OF THIS CODE. SEE FBC,EB 301.5.
  
 2. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS THERE IS
 RECONFIGURATION OF SPACES SHOWN ON PLANS. IN LEVEL 2
 ALTERATIONS, RECONFIGURED SPACES INTENDED FOR OCCUPANCY
 SHALL BE PROVIDED WITH MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL IN ACCORDANCE WITH FBC,EB 609.1. SHOW
 OUTSIDE AIR CALCULATIONS BASED ON OCCUPANCY
 CLASSIFICATION, OCCUPANT LOADS AND VENTILATION RATES AS
 REQUIRED BY FBC,M TABLE 403.3. BE SURE TO INCLUDE
 RESTROOM EXHAUST.
  
 3. ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC,EB
 611.1. BASIC PRESCRIPTIVE REQUIREMENTS SHALL BE MET FOR
 ALL BUILDINGS WITH REGARD TO NEW COMPONENTS BEING
 INSTALLED OR COMPONENTS BEING RETROFITTED (SUCH AS
 LIGHTING, NEW WINDOW AND NEW DUCTS) IN ACCORDANCE WITH
 FBC 13-400.1. PROVIDE DOCUMENTATION AND SUFFICIENT
 NOTATION ON PLAN TO DEMONSTRATE COMPLIANCE WITH THESE
 SECTIONS.
  