| 2007-10-14 15:06:18 | ** DENIED** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL |
| | PANEL IS NOT PERMITTED IN THE STORAGE ROOM. THIS IS A |
| | LIFE SAFETY AND FIRE HAZARD AND EVEN THOUGH THIS IS |
| | BEING SHOWN AS EXISTING, THIS WILL BE REQUIRED TO BE |
| | ADDRESSED AT THIS TIME. |
| | PLEASE SEE 240.24D, 408.17, 110.26 ETC |
| | |
| | 3) NOTE: PLEASE PROVIDE MAXIMUM LIGHTING DENSITIES PER |
| | 13-415.2 FOR NEW AREAS/NEW LIGHTING. |
| | PLEASE SEE TABLE B. |
| | PLEASE ALSO SEE THAT AN *NEW* LIGHTING CONTROLS BEING |
| | INSTALLED MUST MEET 13-415.1.ABC.1.1, .1.2. THIS IS |
| | ONLY FOR NEW DEVICES. 13-101 |
| | PLEASE SPECIFY THE MAXIMUM TIMES FOR DEVICE(S) CHOSEN. |
| | |
| | 4) NOTE: PLEASE CLARIFY PLANS AS NOW RISER INDICATES |
| | TWO METERS AND MAIN DISCONNECTS TO A SINGLE TENANT. |
| | PLEASE BE AWARE OF A SINGLE OCCUPANCY WITH ONLY ONE |
| | METER PER BUILDING AND ZONING. (METER MAY BE REQUIRED |
| | TO BE CHANGED OUT TO A SINGLE METER.) |
| | ** THIS IS ONLY NOTED AS THIS COULD AFFECT EXISTING |
| | RISER AS SHOWN. |
| | ** LABEL ALL MAINS/DISCONNECTS |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR |
| | REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS |
| | SUBMITTED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |