Plan Review Notes
Plan Review Notes For Permit 07090539
Permit Number 07090539
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-13 12:33:38 
 BUILDING PLAN REVIEW
 PERMIT: 07090539
 ADD: 5601 CORPORATE WAY SUITE 200-204
 CONT: CLAY KOHLMEYER GEN. CONT, INC
 TEL: (561)694-1214
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 10/13/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2006 AMENDMENTS.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING.
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
 ) NUMBER OF FLOORS
 ) SQ. FT. FOOTPRINT
  
 5)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
 6)SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST
 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS. CLEAR FLOOR SPACE 11-4.24.5. A CLEAR
 FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK. NO DOORS IN THIS AREA.
  
 7)FBC 11-7.2 (2) (I)SUBMIT A FRONT ELEVATION DETAIL
 DRAWING WITH DIMENSIONS SHOWING THAT A PORTION OF THE
 MAIN COUNTER IS A MINIMUM 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES.
  
 8)INDICATE BY CIRCLING OR HI-LIGHT WHICH TYPE OF
 WINDOW WILL BE USED FROM THE PRODUCT APPROVAL PACKAGE.
 ON THE DRAWINGS, SUBMIT AN ELEVATION SECTION ON THE NEW
 WINDOW INDICATING THE SIZE OF THE WINDOW WITH THE
 DESIGN PRESSURE, ALSO MARK THE PAGES OF THE PRODUCT
 APPROVAL IN REFERENCE TO THE INSTALLATION OF THE
 WINDOW.
  
 NOTE:ADDITIONAL NOTES MAY APPEAR ON NEXT REVIEW
 ACCORDING THE RESPONSE.
  
 MYRON JACOBS
 BUILDING PLANS REVIEWER
 (561) 805-6726
 [email protected]