| 2007-12-05 15:56:26 | ****CORRECTIONS**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.SEE 11-4.9.4, HANDRAILS FOR STAIRS, AND REVISE |
| | PLANS. |
| | |
| | 4TH REVIEW, NOT ADDRESSED.EXTENSIONS AT TOP AND |
| | BOTTOM NOT PROPERLY SHOWN.PLEASE SEE THE CODE |
| | REFERENCE AND SHOW ALL HANDRAIL EXTENSION DIMENSIONS. |
| | ALSO SEE FBC 11 FIGURES 18 AND 19. |
| | |
| | 2.SEE 11-4.8.5, HANDRAILS FOR RAMPS, AND REVISE |
| | PLANS. |
| | |
| | SEE ITEM 1.PLEASE SHOW EXTENSIONS INCLUDING ALL |
| | DIMENSIONS TO SHOW CODE COMPLIANCE. |
| | |
| | 3.ADDRESSED. |
| | |
| | 4.NO PICKET SPACING OR ANY OTHER DIMENSIONS SHOWN FOR |
| | THE STAIRS.PLEASE SEE FBC1009 AND SHOW COMPLIANCE. |
| | |
| | 5.ENGINEER'S DESIGN IS FOR A POOL RAILING.SEE |
| | FBC1009, FBC1607.STATE DESIGN CRITERIA FOR HANDRAILS. |
| | IT IS NOT CLEAR IF GUARDRAIL STRENGTH IS REQUIRED AS |
| | RISE WAS NOT SHOWN AS REQUESTED. |
| | |
| | 6.SHOW RISE FOR RAMP.SEE FBC1012.1. |
| | |
| | 7.RAILING HEIGHT ON SHEET 1 (38") CONFLICTS WITH |
| | SHEET 2 (42"). |
| | |
| | 8.THIS IS NOT CONSIDERED A RAMP IF THE SLOPE IS LESS |
| | THAN 1:20, FBC11-3.IF IT IS NOT A RAMP, THE HANDRAIL |
| | EXTENSIONS ARE NOT REQUIRED TO COMPLY WITH FBC11-4.8. |
| | HAVE THE ENGINEER REVISE THE PLAN TO SHOW THE SLOPE. |
| | |
| | 9.HANDRAILS ARE REQUIRED AT BOTH SIDES OF STAIRS AND |
| | RAMPS, FBC11-4.8.5(1), 11-4.9.4.THE EXCEPTION NOTED |
| | BY CONTRACTOR IN AN EMAIL IS FOR GUARDRAILS. A |
| | GUARDRAIL IS NOT REQUIRED, BUT HANDRAILS ARE REQUIRED. |
| | |
| | |
| | 10.A 4X PLAN REVIEW FEE HAS BEEN CHARGED, |
| | FS553.80(2)(B), AS REQUIRED BY FLORIDA STATUTE, SEE |
| | ATTACHED.THIS FEE WILL BE CHARGED EVERY TIME THE |
| | COMMENTS ARE NOT ADDRESSED. |