| Plan Review Notes For Permit 07090519 |
| Permit Number |
07090519 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-12-28 10:23:24 | | | | *** REDLINED PLANS*** | | | | | | 1) THE CONDUIT AND CONDUCTORS FROM METER TO MAIN | | | BREAKER PANEL SHALL BE INSTALLED UNDERGROUND/IN SLAB. | | | 230.70, 230.71. | | | IF THIS IS NOT DONE, A MAIN WITH OVER CURRENT | | | PROTECTION WILL BE REQUIRED OUTSIDE ALONG WITH AN | | | EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | | | | 2)KITCHEN WALL AS NOTED ON PREVIOUS REVIEW MUST MEET | | | 210.52 FOR RECEPTACLE SPACING. RECEPTACLE SHOWN IS NOT | | | WITHIN 6FT OF DOOR WAY. | | | | | | 3) PLANS SHOW TWO GARAGE DOOR OPENERS HOWEVER PANEL | | | SCHEDULE ONLY SHOWS ONE CIRCUIT. | | | PLEASE SEE 430.248 AS THE HP RATING OF EACH MOTOR MAY | | | REQUIRE TWO SEPARATE CIRCUITS BEING DEDICATED. | | | | | | 4) LOW VOLTAGE SHOWN ON PLAN REQUIRES A SEPARATE | | | PERMIT. PLANS SHOW PHONE AND CATV ONLY. | | | MAY REFERENCE THESE PLANS FOR CATV AND PHONE. | | | ANY OTHER SYSTEMS INSTALLED (IE: ) SPEAKERS, WILL | | | REQUIRED PLANS/LAYOUT OF LOCATIONS. | | | | | | IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE DO NOT | | | HESITATE IN CONTACTING THIS REVIEWER DIRECTLY. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|