| 2007-11-20 15:49:15 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE KNOW AS PLANS ARE ONLY NOW BEING COMPLETED |
| | AND SUBMITTED FOR ELECTRICAL REVIEW THERE ARE SEVERAL |
| | NEW COMMENTS. THESE COMMENTS COULD NOT HAVE BEEN MADE |
| | ON PREVIOUS PLANS SUBMITTED.. |
| | |
| | 1) NOTE:PLEASE COMPLETE TITLE BLOCKS WITH LICENSE |
| | INFORMATION AND ADDRESS INFORMATION WHICH COORDINATES |
| | WITH THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION. |
| | PLEASE SEE IT SEEMS THE LAST NUMBER OF THE LICENSE |
| | NUMBER IS NOT BEING PRINTED ON SHEETS. THIS COULD HAVE |
| | BEEN REDLINED, HOWEVER PLANS WERE COMING BACK FOR OTHER |
| | COMMENTS. |
| | PLEASE SEE THE ADDRESS ON THE STATE SITE DOES NOT |
| | CORRELATE. (743 BISCAYNE ?) |
| | |
| | 2) NOTE: PLEASE SEE PLANS NOW INDICATE AND NEW SERVICE |
| | HOWEVER PLEASE SHOW THE LOCATION OF THE SERVICE |
| | EQUIPMENT ON PLANS. |
| | WE ARE UNABLE TO DETERMINE CODE COMPLIANCE WITH MANY |
| | ITEMS WITHOUT THESE SHOWN ON PLANS. |
| | 110.26, 240.24, 230.70, 230.71 ETC |
| | |
| | 3) NOTE: PLEASE SEE THE SCALE ON ELECTRICAL PLANS IS |
| | BEING SHOWN AS QUARTER INCH PER FOOT; HOWEVER THIS DOES |
| | NOT CORRELATE WITH THE REST OF THE PLANS/SHEETS. PLEASE |
| | SEE MECHANICAL PLANS FOR EXAMPLE AS THE SAME SCALE IS |
| | SHOWN YET THE LAYOUT IS SUBSTANTIALLY DIFFERENT. |
| | PLEASE KNOW THAT REVIEW FOR SOME ITEMS SUCH AS |
| | RECEPTACLE SPACING CAN NOT BE DONE AT THIS TIME. |
| | FBC 106.3.5.4, 106.3.1, 106.1 |
| | |
| | 4) NOTE: PLEASE SEE 210.52 AS SOME RECEPTACLES ARE |
| | MISSING FOR RULING. |
| | PLEASE SEE KITCHEN WALL FOR EXAMPLE WHERE NO |
| | RECEPTACLES ARE BEING SHOWN. (ONE LOCATION NOTED |
| | ONLY). |
| | |
| | 5) NOTE: PLEASE SEE RISER SHOWS AN EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THE NEW METER TO THE FIRST MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED. |
| | PLEASE SEE 240.24, 250.6. |
| | |
| | 6)NOTE: PLEASE SEE MISSING LOAD FOR DINING AS |
| | REQUIRED PER 210.52B1, 220.53. |
| | PLEASE SEE THAT ONE OR *MORE* OF THE REQUIRED CIRCUITS |
| | EACH REQUIRE 1500VA. |
| | |
| | 7) NOTE: PLEASE SEE 220.54 AS THE MINIMUM VA FOR THE |
| | DRYER SHALL BE 5KVA. |
| | (PLANS SHOW 4). |
| | |
| | 8) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON |
| | PLANS. SOME ITEMS CAN NOT BE REVIEWED FOR CODE |
| | COMPLIANCE AT THIS TIME. |
| | |
| | 9) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOAD |
| | CALCULATIONS ARE MISSING THE REQUIRED DEDICATED |
| | CIRCUIT(S) FOR GDO/ GARAGE DOOR OPENERS. |
| | 430.148, 310.16, 240.4, 220. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE VERIFY 350MCM FOR SERVICE ENTRANCE |
| | CONDUCTORS. THIS IS NOT A CODE ISSUE HOWEVER IF SHOWN |
| | AS 350MCM ON PLANS, THIS IS WHAT WILL BE REQUIRED TO BE |
| | INSTALLED. THIS IS ONLY NOTED FOR INFORMATION ONLY. |
| | |
| | 11) NOTE: PLEASE MAKE NOTE FOR SECTION OF FBC |
| | 13-606.1.ABC.1.2.4 FOR TYPE OF RECESSED LIGHTING |
| | FIXTURES. |
| | |
| | 12) NOTE: PLEASE SEE THERE ARE SOME LIGHTING FIXTURES |
| | ON PLANS WHICH DO NOT INDICATE ANY CONTROLS. |
| | PLEASE SEE FOR EXAMPLE WHAT APPEAR TO BE MASTER BEDROOM |
| | LIGHTS. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE 210.8A2 FOR REQUIRED GFI |
| | RECEPTACLES IN GARAGE. |
| | MISSING GFI DESIGNATION(S). |
| | |
| | 14) NOTE: PLEASE SEE 210.8A3 AS ALL RECEPTACLES OUTSIDE |
| | ARE ALSO REQUIRED TO BE GFI. PLEASE SEE MISSING |
| | DESIGNATIONS. |
| | |
| | 15) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING |
| | RECEPTACLE(S) PER 210.52C2 AND 4. |
| | PLEASE SEE THIS IS FOR WHAT IS SHOWN AS A SECOND |
| | ISLAND. |
| | PLEASE CLARIFY THE RECEPTACLE AS SHOWN. THIS IS SHOWN |
| | IN SINK OR UNDER SINK. |
| | THIS LOCATION, WALL, COUNTER SPACE IS UNCLEAR AT THIS |
| | TIME. |
| | |
| | ** PLEASE KNOW AS SOME ITEMS WERE NOT SHOWN AT THIS |
| | TIME, SOME ITEMS COULD NOT BE DETEMINED. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |