| Date |
Text |
| 2007-09-23 09:40:44 | |
| | ** DENIED** |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE THAT ALL THREE SETS OF PLANS |
| | SUBMITTED ARE PHOTO-COPIES AND ARE NOT ORIGINAL SIGNED, |
| | DATED AND SEALED PLANS AS REQUIRED PER FS 481.221. |
| | ** PLEASE KNOW THAT FOR A SINGLE FAMILY DWELLING ONLY |
| | TWO SIGNED, DATED AND SEALED SETS ARE NEEDED. |
| | IF A THIRD SET IS DESIRED FOR STAMPING/DUPLICATE, THEN |
| | A THIRD SET OF SIGNED, DATED AND SEALED PLANS MAY BE |
| | PROVIDED FOR STAMPING. |
| | |
| | 3) NOTE: PLEASE ADJUST AND COMPLETE TITLE BLOCK WITH |
| | ALL LICENSE INFORMATION NEEDED. PLEASE SEE TITLE BLOCKS |
| | STILL INDICATE MR. LITTLE. THIS REVIEWER HAS BEEN IN |
| | CONTACT WITH MR. ROY FOR REQUIRED |
| | INFORMATION/ADJUSTMENTS. |
| | FAC 61G1-16.004, FS 481.219. |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR |
| | REVIEW FOR CODE COMPLIANCE WITH THE PREVIOUS NOTED |
| | CODES ABOVE. PLEASE SEE NFPA-70 (NEC 2005) AND |
| | NFPA-72. |
| | ALL THREE SETS DO NOT CONTAIN ELECTRICAL PLANS. FBC |
| | 106.1.2, 106.1.3, 106.3.5.4 |
| | PLEASE PROVIDE PANEL SCHEDULE(S) WITH ALL MINIMUM |
| | REQUIRED CIRCUITS PER NEC. 408.4, 240.4, 310.16, |
| | 210.52, 210.11, 220, 215.5 ETC |
| | PLEASE PROVIDE ALL CONDUCTOR SIZES IN PANEL(S) ALONG |
| | WITH CONDUCTORS SIZES.240.4, 310.16 |
| | PLEASE PROVIDE A RISER DIAGRAM FOR NEW OR EXISTING |
| | PROPOSED SERVICE COMPLETE WITH ALLCONDUCTOR SIZES, |
| | CONDUITS, FEEDERS, GROUNDING, AIC RATINGS AND OVER |
| | CURRENT PROTECTION DEVICES. |
| | 230.70, 230.71, 1100.9, 230.72, 230.76, 230.79, 310.16, |
| | 250.50, 240.4 ETC |
| | PLEASE PROVIDE ALL SMOKE ALARM LOCATIONS INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS PER NFPA-72 11.5.1.1, |
| | 11.8.3. FBC R313, FBC 905.2, ETC. |
| | PLEASE PROVIDE ALL RECEPTACLE LOCATIONS REQUIRED PER |
| | ALL OF 210.52 |
| | PLEASE PROVIDE ALL LIGHTING AND CONTROL LOCATIONS PER |
| | 210.70, LS 101 7.8. |
| | PLEASE BE SURE TO PROVIDE LISTING OF ALL ARC FAULT |
| | PROTECTED CIRCUITS PER 210.12. |
| | PLEASE PROVIDE ALL DISCONNECTING MEANS FOR EQUIPMENT AS |
| | REQUIRED. 440.11, 422.30, 422.31. |
| | PLEASE PROVIDE LOAD CALCULATIONS FOR ALL ELECTRICAL |
| | FROM NEW OR EXISTING SERVICE. NEC 220.**PLEASE BE SURE |
| | TO SEE THE NEW 2005 CODE WITH RESPECT TO WATER HEATERS |
| | TO BE FIGURED AT 125% PER 422.13. |
| | PLEASE SUBMIT ENERGY CALCULATIONS PER FBC CHAPTER 13. |
| | PLEASE BE SURE TO REFERENCE ANY RECESSED LIGHTING PER |
| | FBC 13-606.1.ABC.1.2.4 FOR *AIR MOVEMENT* ALLOWANCES |
| | FROM CONDITIONED SPACE. |
| | |
| | ** PLEASE SEE SOME OF THE ITEMS REFLECT ABOVE ARE IN NO |
| | WAY ALL ITEMS IN THE NEC WHICH WILL BE REVIEWED. |
| | THE ITEMS ABOVE ARE FOR ITEMS NEEDED, AS EACH DWELLING |
| | AND SCOPE OF WORK VARIES AND PLANS WERE NOT SUBMITTED |
| | FOR REVIEW IT IS NOT POSSIBLE TO GIVE CODE COMPLIANT |
| | REVIEW AT THIS TIME. |
| | PLEASE KNOW THERE MAY VERY WELL BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH COULD NOT BE MADE AT THIS TIME. |
| | **IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |