| 2007-10-09 16:35:59 | |
| | |
| | DENIED |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $ FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, |
| | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 7)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 8)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL COVER |
| | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| | SUBMITTED APPLICATIONS WILL BE DENIED |
| | |
| | 9)NO PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR |
| | DOORS, WINDOWS, GARAGE DOORS, LINTELS, MULLIONS FOR |
| | JOINED WINDOWS, ROOFING,CONNECTORS AND STRAPS (OR ADD |
| | FLORIDA PRODUCT APPROVAL NUMBERS TO THE CONNECTOR |
| | SCHEDULE), ETC. |
| | |
| | 10)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| | PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA |
| | STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND |
| | DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC |
| | 2004. THE EXEMPTION FROM LICENSURE UNDER 481.229 FS |
| | DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR THE |
| | DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS. |
| | |
| | 11)PROVIDE STRUCTURAL DETAIL FOR THE FRONT PORCH AREA |
| | THAT SHOWS POST TO BEAM CONNECTION AND BEAM TO WALL AT |
| | MAIN HOUSE, ETC. |
| | |
| | 12)REAR COLUMNS DO NOT SHOW BEAM ABOVE OR IT'S |
| | DIMENSIONS FOR SUPPORT OF ROOF |
| | |
| | 13)PROVIDE DETAIL OF GARAGE DOOR BUCK IF NOT STATED |
| | IN THE PRODUCT APPROVAL |
| | |
| | 14)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL |
| | |
| | 15)PROVIDE MIN. R-VALUE OF WALL AND CEILING |
| | INSULATION, BE SURE TO MATCH THE VALUES IN THE ENERGY |
| | CALC'S |
| | |
| | 16)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 17)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| | REQUIRED PER R807.1 FBC RES. |
| | |
| | 18)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER |
| | R322.1.1 FBC |
| | |
| | 19)THE SOIL REPORT PERFORMED BY THE GEOTECHNICAL |
| | ENGINEER STATES A BEARING CAPACITY OF 2000 PSF AND THE |
| | BUILDING HAS BEEN DESIGNED ON AN ASSUMED BEARING OF |
| | 3000 PSF |
| | |
| | 20)PROVIDE DETAIL OF SEPARATION BETWEEN GARAGE AND |
| | RESIDENCE FOR WALLS AND DOOR PER R309.1 AND R309.2 FBC |
| | RES. |
| | |
| | 21)PROVIDE SIZE OF ATTIC VENTILATION THAT MEETS THE |
| | REQUIREMENTS OF R806.2 FBC RES. |
| | |
| | 22)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |