| 2007-09-26 15:36:17 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING |
| | CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC |
| | AS |
| | AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. DECLARE SAME ON THE PLAN. |
| | |
| | 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE PLAN |
| | TO INDICATE COMPLIANCE. |
| | |
| | 5} REGARDING THE AHU IN THE BATHROOM PER 240.24(E) IN |
| | DWELLING UNITS AND GUEST ROOMS OR GUEST SUITES OF |
| | HOTELS AND MOTELS, OVERCURRENT DEVICES, OTHER THAN |
| | SUPPLEMENTARY OVERCURRENT PROTECTION, SHALL NOT BE |
| | LOCATED IN BATHROOMS. |
| | |
| | 6} LOCATE THE CONDENSING UNIT ON THE PLAN. ALSO SHOW |
| | COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14, |
| | RECEPTACLE PER 210.63. ALSO NOTE ZONING WILL NEED TO |
| | SEE THE LOCATION FOR SETBACK REQUIREMENTS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |