| Date |
Text |
| 2007-09-26 16:12:04 | |
| | |
| | APPLICATION # 07090500 |
| | ELECTRICAL PLAN REVIEW |
| | 1386 9TH COURT |
| | |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING |
| | CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC |
| | AS |
| | AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE, GROUNDING DETAILS,PANEL SCHEDULES, |
| | SERVICE EQUIPMENT AND PANEL LOCATIONS PER 106.3.5.4 |
| | FBC. 215.5NEC. NOTE #6 INDICATES A SERVICE TO A NEW |
| | SHED, INCLUDE ON THE RISER DIAGRAM. PHYSICALLY LOCATE |
| | ALL SERVICE EQUIPMENT ON THE PLAN. |
| | |
| | 3} SHOW THE LOCATION OF THE A/C CONDENSER ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14,RECEPTACLE PER 210.63 |
| | |
| | 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). INDICATE COMPLIANCE IN THE |
| | PANEL SCHEDULE. |
| | |
| | 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. INDICATE |
| | COMPLIANCE ON THE PLAN. |
| | |
| | 6} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |