Plan Review Notes
Plan Review Notes For Permit 07090496
Permit Number 07090496
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-15 11:42:36**** DENIED 2ND REVIEW****
  
 ** PLANS RECEIVED FROM ADDRESSING 10/11
  
 1) NOTE: PLEASE SEE THE ADDRESSING COMMENTS ARE THE
 SAME AS PREVIOUS REVIEW. ELECTRICAL SIGN OFF CAN NOT BE
 ACHIEVED UNTIL ADDRESSING HAS BEEN CORRECTED AND
 COORDINATED WITH PLANS.
 PLEASE SEE THE PLANS/TITLE BLOCKS DO NOT INDICATE THE
 CORRECT LOCATION, STILL INDICATES HAWTHORNE SUITES.
 FA C61G15-23.002
  
 2) NOTE: PLEASE SEE RISER IS STILL INDICATING AN
 *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED. THIS IS SHOWN
 FROM BOTH THE FPL TRANSFORMER AND FROM METER TO MAIN.
 250.6, 250.24B.
 ** EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 3) NOTE: PLEASE SEE THE RISER IS INDICATING NOTE #6 AS
 *FUTURE*, YET THERE ARE SEVERAL LOCATIONS WHICH THIS #6
 WOULD NEED TO BE INSTALLED AT THIS TIME.
 PLEASE SEE FOR EXAMPLE THE #6 FROM MAIN, TO ATS, ATS TO
 PANEL ETC.
  
 4) NOTE: PLEASE VERIFY GROUNDING ELECTRODE FOR
 SEPARATELY DERIVED SYSTEM PER 250.50, 250.20, AND
 250.30.
 COULD NOT LOCATE THIS SYSTEM.
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE ATS WHICH IS BEING INSTALLED AT THIS
 TIME.
 THE GENERATOR IS THE ITEM THAT WILL BE FUTURE.
 90.7, 110.3
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-05 11:19:49SENT TO ADDRESSING. NEEDS ADDRESSING BEFORE
 ELECTRICAL.
 PERMIT APPLICATION NOT CORRECTED.