| Date |
Text |
| 2007-10-15 11:42:36 | **** DENIED 2ND REVIEW**** |
| | |
| | ** PLANS RECEIVED FROM ADDRESSING 10/11 |
| | |
| | 1) NOTE: PLEASE SEE THE ADDRESSING COMMENTS ARE THE |
| | SAME AS PREVIOUS REVIEW. ELECTRICAL SIGN OFF CAN NOT BE |
| | ACHIEVED UNTIL ADDRESSING HAS BEEN CORRECTED AND |
| | COORDINATED WITH PLANS. |
| | PLEASE SEE THE PLANS/TITLE BLOCKS DO NOT INDICATE THE |
| | CORRECT LOCATION, STILL INDICATES HAWTHORNE SUITES. |
| | FA C61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE RISER IS STILL INDICATING AN |
| | *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS |
| | OF DISCONNECT WHICH IS NOT PERMITTED. THIS IS SHOWN |
| | FROM BOTH THE FPL TRANSFORMER AND FROM METER TO MAIN. |
| | 250.6, 250.24B. |
| | ** EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 3) NOTE: PLEASE SEE THE RISER IS INDICATING NOTE #6 AS |
| | *FUTURE*, YET THERE ARE SEVERAL LOCATIONS WHICH THIS #6 |
| | WOULD NEED TO BE INSTALLED AT THIS TIME. |
| | PLEASE SEE FOR EXAMPLE THE #6 FROM MAIN, TO ATS, ATS TO |
| | PANEL ETC. |
| | |
| | 4) NOTE: PLEASE VERIFY GROUNDING ELECTRODE FOR |
| | SEPARATELY DERIVED SYSTEM PER 250.50, 250.20, AND |
| | 250.30. |
| | COULD NOT LOCATE THIS SYSTEM. |
| | |
| | 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE ATS WHICH IS BEING INSTALLED AT THIS |
| | TIME. |
| | THE GENERATOR IS THE ITEM THAT WILL BE FUTURE. |
| | 90.7, 110.3 |
| | FBC 106.1.2 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF |
| | THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-10-05 11:19:49 | SENT TO ADDRESSING. NEEDS ADDRESSING BEFORE |
| | ELECTRICAL. |
| | PERMIT APPLICATION NOT CORRECTED. |