| 2007-09-27 14:04:29 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE VERIFY OWNER, PROPOERTY INFORMATION AS |
| | PERMIT WAS APPLIED FOR UNDER 301 LAMBERTON WHICH IS A |
| | SEPARATE PCN. |
| | PLEASE VERIFY LOCATION OF LEFT STATION AND WHETHER OR |
| | NOT THIS IS ON PRIVATE PROPERTY ? |
| | PLEASE SEE ANY COMMENTS FROM ADDRESSING. |
| | |
| | 2) NOTE: PLEASE SEE THIS IS BEING APPLIED AS AN |
| | ELECTRICLA PERMIT ALTHOUGH PLANS ARE FOR A GENERATOR |
| | ALSO. |
| | IF A GENERATOR IS BEING PROPOSED, A PERMIT APPLICATION |
| | FOR THIS UNIT WHICH WOULD INCLUDE ALL ITEMS GIVEN TO |
| | THE WEITZ COMPANY AT MEETING DATED 9/27 WOULD BE NEEDED |
| | FOR SUBMISSION. |
| | |
| | ** PLEASE DETERMINE SCOPE AND APPLY ACCORDINLY. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |