Plan Review Notes
Plan Review Notes For Permit 07090495
Permit Number 07090495
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-05 12:06:37 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE THAT THE PREVIOUS REVIEW NOTES REQUESTED
 TO GO OVER ELECTRICAL PLANS FOR COORDINATION BEFORE
 RESUBMITTING AS THERE WERE SEVERAL ITEMS WHICH NEEDED
 TO MEET 2005 NEC>
 AT THAT TIME A FULL REVIEW WAS NOT DONE AND IT WAS
 STATED AS SUCH.
 PLEASE SEE COMMENTS BELOW.
  
  
 1) NOTE:PLEASE SEE THE CONDUIT ON THE RISER FOR THE
 SERVICE ENTRANCE CONDUCTORS IS BEING SHOWN AS A 4INCH
 CONDUIT. HOW IS THIS POSSIBLE WHEN THE METER-CAN WILL
 NOT BE LARGE ENOUGH TO ACCOMMODATE THIS SIZE CONDUIT?
 PLEASE ALSO SEE THE RISER UP TO METER-CAN ALSO
 INDICATES CONDUIT AS SCHEDULE 40, THIS WOULD BE
 REQUIRED TO BE SCHEDULE 80 AS THIS IS A LOCATION
 SUBJECT TOPHYSICAL DAMAGE. 352.10F
 PLEASE ADJUST.
 FBC 106.1.2 FOR COORDINATION.
  
 2) NOTE: PLEASE INDICATE AMPERAGE OF METER-CAN.
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE CLARIFY THE LOAD SHOWN ON PANEL *N* FOR
 LIGHT POLES. THE PLANS INDICATE 3-POLES, EACH WITH 250W
 FIXTURES. WHERE DOES THE LOAD AS SHOWN COME FROM?
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125% INCLUDING
 PUMPS AND OTHER LIGHTING WHICH IS EXPECTED TO RUN FOR 3
 OR MORE HOURS AS DEFINED IN ART 100 OF THE NEC.
 PLEASE SEE 215.3, 230.42 ETC FOR LOADS.
 PLEASE REVISE CALCULATIONS INCLUDING LOADS ON THE
 AQUAGENIX PANEL.
  
 4) NOTE: PLEASE SEE THE RISER IS SHOWING *EQUIPMENT
 GROUNDING CONDUCTOR* BEING INSTALLED ON THE LINE SIDE
 OF THE METER FROM FPL TRANSFORMER. PLEASE ALSO SEE THE
 RISER ALSO INDICATES THIS SAME EQUIPMENT GROUND FROM
 THE METER TO THE MAIN (FIRST MEANS OF DISCONNECT) WHICH
 IS NOT PERMITTED.
 PLEASE SEE 250.24B, AND 250.6. AS THE GROUNDED/NEUTRAL
 CONDUCTOR IS REQUIRED TO BE BONDED AT THIS FIRST MEANS
 OF DISCONNECT, IF AN EQUIPMENT GROUNDING CONDUCTOR WAS
 INSTALLED AHEAD OF THIS MAIN, THIS WOULD CREATE
 OBJECTIONABLE CURRENTS.
 PLEASE ADJUST RISER AND NOTES AND REMOVE.
  
 5) NOTE: PLEASE KNOW THAT NO ELECTRICAL LIGHTING
 FIXTURES/EQUIPMENT OF ANY KIND WILL BE PERMITTED TO BE
 IN POOL AREA AND ELECTRICAL WHICH IS BEING FED FROM THE
 MAIN HOTEL WHICH IS A SEPARATE ELECTRICAL SERVICE.
 POOL AREA ELECTRICAL SHOULD BE SEPARATED.
 PLEASE BE SURE TO ADJUST ANY LOCATIONS IN WHICH THIS
 MAY THE SITUATION.
 THIS IS ONLY BEING NOTED FOR INFORMATION.
  
  
 IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS
 REVIEW
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  