Plan Review Notes
Plan Review Notes For Permit 07090490
Permit Number 07090490
Review Stop E
Sequence Number 3
Notes
Date Text
2008-06-13 16:16:52** DENIED **
  
 1) NOTE: PLEASE SEE COMMENT WITH RESPECT TO GROUND
 FAULT ON ELECTRICAL SERVICE ALONG WITH GROUND FAULT
 SENSING IS STILL A COMMENT. AS STATED ON PREVIOUS
 REVIEWS ALL MANUFACTURES WHITE PAPERS AND DOCUMENTS
 READ BY THIS REVIEWER INDICATE A COORDINATION LOSS
 BETWEEN THE MAIN, ATS AND SYSTEM WHEN A FOUR POLE UNIT
 IS NOT INSTALLED.
 PLEASE PROVIDE DOCUMENTATION FROM THE PROPOSED
 MANUFACTURE ASCO WHICH SHOWS AND STATES THIS IS NO
 LONGER AN ISSUE OR IS NOT AN ISSUE FOR THE GROUND FAULT
 PROTECTION ON PRIMARY AND GROUND FAULT SENSING ON THE
 GENERATOR AND SECONDARY SIDE OF EQUIPMENT.
 110.3, 90.7, 240.13, 230.95, 700.26, 700.7D, 701.17,
 NFPA-110 6.2.15.
 THE RESPONSE LETTER MENTIONS THIS SYSTEM DOES NOT
 AFFECT OTHER EMERGENCY POWER IN THE BUILDING. WHAT ARE
 THE OTHER EMERGENCY POWER SOURCES FOR BACK UP OF
 EMERGENCY AND LEGALLY REQUIRED SYSTEM?
 THE RESPONSE MENTIONS THAT THE NEUTRAL AND GROUND BOND
 TO BE REMOVED AT THE GENERATOR AS WELL AS THIS WAS
 NOTED ON PLANS.
 THIS WAS NOT MY PREVIOUS COMMENT. IF A FOUR POLE
 TRANSFER SWITCH IS REQUIRED TO PROVIDE COORDINATION,
 THEN THE GENERATOR WOULD BE REQUIRED TO BE SEPARATELY
 DERIVED.
  
 2) NOTE: PLEASE BE SURE TO PLACE ALL PLANS INTO AN
 ATTACHED ORDERLY FASHION. NEW SHEETS SHOULD BE SEPARATE
 INTO TWO SETS WITH OLD SHEETS ATTACHED TO EACH OTHER
 SEPARATELY.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  