| 2008-06-13 16:16:52 | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE COMMENT WITH RESPECT TO GROUND |
| | FAULT ON ELECTRICAL SERVICE ALONG WITH GROUND FAULT |
| | SENSING IS STILL A COMMENT. AS STATED ON PREVIOUS |
| | REVIEWS ALL MANUFACTURES WHITE PAPERS AND DOCUMENTS |
| | READ BY THIS REVIEWER INDICATE A COORDINATION LOSS |
| | BETWEEN THE MAIN, ATS AND SYSTEM WHEN A FOUR POLE UNIT |
| | IS NOT INSTALLED. |
| | PLEASE PROVIDE DOCUMENTATION FROM THE PROPOSED |
| | MANUFACTURE ASCO WHICH SHOWS AND STATES THIS IS NO |
| | LONGER AN ISSUE OR IS NOT AN ISSUE FOR THE GROUND FAULT |
| | PROTECTION ON PRIMARY AND GROUND FAULT SENSING ON THE |
| | GENERATOR AND SECONDARY SIDE OF EQUIPMENT. |
| | 110.3, 90.7, 240.13, 230.95, 700.26, 700.7D, 701.17, |
| | NFPA-110 6.2.15. |
| | THE RESPONSE LETTER MENTIONS THIS SYSTEM DOES NOT |
| | AFFECT OTHER EMERGENCY POWER IN THE BUILDING. WHAT ARE |
| | THE OTHER EMERGENCY POWER SOURCES FOR BACK UP OF |
| | EMERGENCY AND LEGALLY REQUIRED SYSTEM? |
| | THE RESPONSE MENTIONS THAT THE NEUTRAL AND GROUND BOND |
| | TO BE REMOVED AT THE GENERATOR AS WELL AS THIS WAS |
| | NOTED ON PLANS. |
| | THIS WAS NOT MY PREVIOUS COMMENT. IF A FOUR POLE |
| | TRANSFER SWITCH IS REQUIRED TO PROVIDE COORDINATION, |
| | THEN THE GENERATOR WOULD BE REQUIRED TO BE SEPARATELY |
| | DERIVED. |
| | |
| | 2) NOTE: PLEASE BE SURE TO PLACE ALL PLANS INTO AN |
| | ATTACHED ORDERLY FASHION. NEW SHEETS SHOULD BE SEPARATE |
| | INTO TWO SETS WITH OLD SHEETS ATTACHED TO EACH OTHER |
| | SEPARATELY. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |