| Plan Review Notes For Permit 07090490 |
| Permit Number |
07090490 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-04 12:14:23 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1. OK | | | | | | 2.OK | | | | | | 3.WHAT SIZE AND WHAT LISTINGS ARE PRESENT FOR THE | | | DIESEL TANK? | | | | | | 4.PLEASE INDICATE WHAT EQUIPMENT THE NEW GENERATOR | | | WILL SUPPLY.IS ANY EMERGENCY EQUIPMENTBEING | | | SUPPLIED POWER FROM THIS EQUIPMENT. | | | | | | 5.OK | | | | | | 6.NO INFORMATION PROVIDED REGARDING ANY WARNING | | | LABELS OR SIGNAGE RELATING TO THE DIESEL TANK | | | INSTALLATION. | | | | | | 7.NO INFORMATION PROVIDED WITH REGARDS TO THE VENTING | | | OF THE DIESEL TANK. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|