| Date |
Text |
| 2008-03-05 12:54:17 | ** DENIED2ND REVIEW ** |
| | |
| | ** IMPORTANT: AS NOTED ON PREVIOUS REVIEW THERE WERE |
| | SEVERAL ITEMS NOT SUBMITTED FOR INITIAL REVIEW AND THAT |
| | THAT MANY OF THESE ITEMS ARE ONLY NOW BEING SUBMITTED |
| | FOR THE FIRST TIME THERE ARE SEVERAL NEW COMMENTS. |
| | ** PLEASE ALSO BE AWARE AS THERE ARE STILL SOME ITEMS |
| | NOT SUBMITTED OR WILL BE CHANGING BASED ON COMMENTS |
| | BELOW A FULL REVIEW FOR CODE COMPLIANCE MAY NOT BE DONE |
| | AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE FBC CHAPTER 27 WHICH STATES ALL |
| | BACK POWER GENERATOR POWER TO BE DONE PER NFPA-110. |
| | THIS DOES NOT STATE WITH THE EXCEPTION TO OPTIONAL |
| | STAND-BY SYSTEMS. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER NOW SHOWS GROUND FAULT |
| | PROTECTION ON THE GENERATOR. PLEASE SEE THE PREVIOUS |
| | REVIEW COMMENT WAS WITH RESPECT TO THE REQUIRED GFP ON |
| | THE PRIMARY SIDE THE SERVICE. PLEASE SEE 230.95 AND |
| | 240.13 WHICH DOES NOT REQUIRE THIS GFP ON THE SECONDARY |
| | EMERGENCY SIDE. PLEASE SEE 700 AND 701 DOES REFLECT THE |
| | DESIRE FOR GROUND FAULT SENSING. PLEASE SEE WHITE |
| | PAPERS FOR SEVERAL MANUFACTURES WITH RESPECT TO |
| | COORDINATION OF THE GFP OF SYSTEMS. THIS OFFICE HAS |
| | FOUND FROM ALL MANUFACTURES REVIEWED TO DATE SPEAK OF |
| | COORDINATION LOSS WHEN THE USE OF A 4-POLEIS NOT |
| | INSTALLED. |
| | ** PLEASE BE AWARE USING THE 4-POLE UNIT WOULD REQUIRE |
| | A SEPARATELY DERIVED GENERATOR SYSTEM. |
| | |
| | A) PLEASE SEE THE PLANS CLEARLY SHOW THE NEW PROPOSED |
| | ATS LOCATED OUTSIDE YET THE BILLING AND ORDER FORMS |
| | CLEARLY SHOW THE ATS AS NEMA 1 RATED WHICH IS ONLY FOR |
| | INDOOR INSTALLATIONS.110.9, 90.7 |
| | PLEASE SEE THAT NO INFORMATION COULD BE LOCATED TO SHOW |
| | THE ATS IS *SERVICE ENTRANCE RATED*. RATING OF SERVICE |
| | EQUIPMENT AND WHETHER OR NOT IT CONTAINS A *MANUAL |
| | MEANS OF DISCONNECT, RATED FOR THE LOAD SERVED* |
| | (230.76, 230.79). |
| | |
| | B) PLEASE SEE THE PLANS INDICATE THE ATS AS 1600AMPS |
| | AND RISER INDICATES THE ATS AS 2000AMPS, AND YET THE |
| | BILLING ORDER SHEETS INDICATE 1200AMPS? |
| | PLEASE COORDINATE. |
| | |
| | 110.3, 90.7 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE CONDUIT DUCT BANK DETAILS WHICH |
| | DOES NOT INDICATE ALL CONDUITS IN FACT THE DETAIL |
| | MENTIONS TYPICAL OF THREE YETBASED ON THE RISER THE |
| | THERE ARE DUCK BANKS WITH 6 AND 4 SETS. |
| | PLEASE COORDINATE AND CLARIFY THESE. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 3) NOTE: PLEASE CLARIFY WHAT THE 1/C IS IN EACH OF THE |
| | CONDUIT/CONDUCTORS NOTES. |
| | FBC 106.1.2 ADDITIONAL INFORMATION. |
| | |
| | 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AND INTENDED |
| | LOADS FOR THE SERVICE. PLEASE SEE 702.5 AS THE |
| | EQUIPMENT NEEDS TO BE RATED FOR THE LOADS TO BE SERVED. |
| | AS THE SERVICE IS 2000AMPS AND THE BREAKER ON THE |
| | GENERATOR IS ONLY 1000AMPS. |
| | PLEASE SUBMIT LOADS. |
| | 220.87 |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |