2008-03-05 12:54:17** DENIED2ND REVIEW **
  
 ** IMPORTANT: AS NOTED ON PREVIOUS REVIEW THERE WERE
 SEVERAL ITEMS NOT SUBMITTED FOR INITIAL REVIEW AND THAT
 THAT MANY OF THESE ITEMS ARE ONLY NOW BEING SUBMITTED
 FOR THE FIRST TIME THERE ARE SEVERAL NEW COMMENTS.
 ** PLEASE ALSO BE AWARE AS THERE ARE STILL SOME ITEMS
 NOT SUBMITTED OR WILL BE CHANGING BASED ON COMMENTS
 BELOW A FULL REVIEW FOR CODE COMPLIANCE MAY NOT BE DONE
 AT THIS TIME.
  
 1) NOTE: PLEASE SEE FBC CHAPTER 27 WHICH STATES ALL
 BACK POWER GENERATOR POWER TO BE DONE PER NFPA-110.
 THIS DOES NOT STATE WITH THE EXCEPTION TO OPTIONAL
 STAND-BY SYSTEMS.
  
 2) NOTE: PLEASE SEE THE RISER NOW SHOWS GROUND FAULT
 PROTECTION ON THE GENERATOR. PLEASE SEE THE PREVIOUS
 REVIEW COMMENT WAS WITH RESPECT TO THE REQUIRED GFP ON
 THE PRIMARY SIDE THE SERVICE. PLEASE SEE 230.95 AND
 240.13 WHICH DOES NOT REQUIRE THIS GFP ON THE SECONDARY
 EMERGENCY SIDE. PLEASE SEE 700 AND 701 DOES REFLECT THE
 DESIRE FOR GROUND FAULT SENSING. PLEASE SEE WHITE
 PAPERS FOR SEVERAL MANUFACTURES WITH RESPECT TO
 COORDINATION OF THE GFP OF SYSTEMS. THIS OFFICE HAS
 FOUND FROM ALL MANUFACTURES REVIEWED TO DATE SPEAK OF
 COORDINATION LOSS WHEN THE USE OF A 4-POLEIS NOT
 INSTALLED.
 ** PLEASE BE AWARE USING THE 4-POLE UNIT WOULD REQUIRE
 A SEPARATELY DERIVED GENERATOR SYSTEM.
  
 A) PLEASE SEE THE PLANS CLEARLY SHOW THE NEW PROPOSED
 ATS LOCATED OUTSIDE YET THE BILLING AND ORDER FORMS
 CLEARLY SHOW THE ATS AS NEMA 1 RATED WHICH IS ONLY FOR
 INDOOR INSTALLATIONS.110.9, 90.7
 PLEASE SEE THAT NO INFORMATION COULD BE LOCATED TO SHOW
 THE ATS IS *SERVICE ENTRANCE RATED*. RATING OF SERVICE
 EQUIPMENT AND WHETHER OR NOT IT CONTAINS A *MANUAL
 MEANS OF DISCONNECT, RATED FOR THE LOAD SERVED*
 (230.76, 230.79).
  
 B) PLEASE SEE THE PLANS INDICATE THE ATS AS 1600AMPS
 AND RISER INDICATES THE ATS AS 2000AMPS, AND YET THE
 BILLING ORDER SHEETS INDICATE 1200AMPS?
 PLEASE COORDINATE.
  
 110.3, 90.7 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE CONDUIT DUCT BANK DETAILS WHICH
 DOES NOT INDICATE ALL CONDUITS IN FACT THE DETAIL
 MENTIONS TYPICAL OF THREE YETBASED ON THE RISER THE
 THERE ARE DUCK BANKS WITH 6 AND 4 SETS.
 PLEASE COORDINATE AND CLARIFY THESE.
 FBC 106.1.2 FOR COORDINATION.
  
 3) NOTE: PLEASE CLARIFY WHAT THE 1/C IS IN EACH OF THE
 CONDUIT/CONDUCTORS NOTES.
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AND INTENDED
 LOADS FOR THE SERVICE. PLEASE SEE 702.5 AS THE
 EQUIPMENT NEEDS TO BE RATED FOR THE LOADS TO BE SERVED.
 AS THE SERVICE IS 2000AMPS AND THE BREAKER ON THE
 GENERATOR IS ONLY 1000AMPS.
 PLEASE SUBMIT LOADS.
 220.87
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  