Plan Review Notes
Plan Review Notes For Permit 07090490
Permit Number 07090490
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-22 10:21:251. THE ENTIRE INSTALLATION TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 2. NO CUT SHEETS OR PRODUCT APPROVALS PROVIDED WITH
 PERMIT APPLICATION.
  
 3. SEVERAL PLANS DECLARES THAT A DIESEL TANK IS
 PROPOSED. WHAT SIZE AND WHAT LISTINGS ARE PRESENT FOR
 THE TANK.
  
 4. PLEASE INDICATE WHAT EQUIPMENT THE NEW GENERATOR
 WILL SUPPLY. IS ANY EMERGENCY EQUIPMENT BEING SUPPLIED
 POWER FROM THIS EQUIPMENT.
  
 5. IS ANY DEVICES PLANNED TO PREVENT THE GENERATOR FROM
 RECEIVING ANY MECHANICAL DAMAGE FROM PASSING VEHICLES.
  
 6. NO INFORMATION PROVIDED REGARDING ANY WARNING LABELS
 OR SIGNAGE RELATING TO THE DIESEL TANK INSTALLATION.
  
 7. NO INFORMATION PROVIDED WITH REGARDS TO THE VENTING
 OF THE DEIESEL TANK.
  
 8. MORE DETAILS NEEDED TO PROVIDE A COMPLETE FIRE PLAN
 REVIEW.
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX