| Plan Review Notes For Permit 07090490 |
| Permit Number |
07090490 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-22 10:21:25 | 1. THE ENTIRE INSTALLATION TO COMPLY WITH NFPA 70, THE | | | NATIONAL ELECTRICAL CODE. | | | | | | 2. NO CUT SHEETS OR PRODUCT APPROVALS PROVIDED WITH | | | PERMIT APPLICATION. | | | | | | 3. SEVERAL PLANS DECLARES THAT A DIESEL TANK IS | | | PROPOSED. WHAT SIZE AND WHAT LISTINGS ARE PRESENT FOR | | | THE TANK. | | | | | | 4. PLEASE INDICATE WHAT EQUIPMENT THE NEW GENERATOR | | | WILL SUPPLY. IS ANY EMERGENCY EQUIPMENT BEING SUPPLIED | | | POWER FROM THIS EQUIPMENT. | | | | | | 5. IS ANY DEVICES PLANNED TO PREVENT THE GENERATOR FROM | | | RECEIVING ANY MECHANICAL DAMAGE FROM PASSING VEHICLES. | | | | | | 6. NO INFORMATION PROVIDED REGARDING ANY WARNING LABELS | | | OR SIGNAGE RELATING TO THE DIESEL TANK INSTALLATION. | | | | | | 7. NO INFORMATION PROVIDED WITH REGARDS TO THE VENTING | | | OF THE DEIESEL TANK. | | | | | | 8. MORE DETAILS NEEDED TO PROVIDE A COMPLETE FIRE PLAN | | | REVIEW. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | 804-4709 PHONE | | | 804-4774 FAX |
|