| Date |
Text |
| 2007-10-14 13:49:27 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO SETS OF PLANS. PLEASE DO NOT |
| | SUBMIT INDIVIDUAL LOOSE SHEETS NOT IN SETS FOR REVIEW. |
| | ONE SET WAS MADE FOR REVIEW OF PLANS BY THIS REVIEWER. |
| | PLEASE BE SURE TO DO THIS UPON THE NEXT RE-SUBMITTAL OF |
| | PLANS. |
| | FBC ADMIN SECTION 106.1 |
| | |
| | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED. |
| | |
| | 3) NOTE: PLEASE SEE COLOR CODING IS REQUIRED TO BE |
| | BROWN, PURPLE AND YELLOW. |
| | THE NEC DOES NOT PROVIDE COLOR CODING AND *ORANGE* IS |
| | BASED ON A HIGH-LEG SYSTEM WHICH THIS IS NOT. THE |
| | CURRENT COLOR CODING IN THIS JURISDICTION FOR THE PAST |
| | 20+ YEARS IS THAT AS BR/PURP/YELL. |
| | 90.4 |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR BOTH THE GENERATOR AND ATS BEING PROPOSED. |
| | PLEASE SEE COMMENTS BELOW AS THERE ARE SEVERAL ITEMS TO |
| | BE REVIEWED FOR CODE COMPLIANCE WHICH CAN NOT BE DONE |
| | AT THIS TIME. |
| | PLEASE BE SURE THE SPECS/CUT SHEETS FOR ANY FUEL TANK |
| | FOR PRIME-MOVER ARE SUBMITTED ALSO. THIS WILL BE |
| | REVIEWED BY OTHER TRADES SUCH AS MECHANICAL, FIRE |
| | MARSHAL ETC. |
| | NEC 90.7, 110.3 ETC |
| | |
| | 5) NOTE: PLEASE SEE 240.13 AND 230.95 AS GF PROTECTION |
| | COULD NOT BE LOCATED. |
| | PLEASE ALSO SEE SPECIFICATIONS FROM MANUFACTURES AS |
| | THIS MAY REQUIRE THIS TO BE A 4-POLE DEVICE WHICH THE |
| | GENERATOR WOULD THEN BECOME AND SEPARATELY DERIVED |
| | SYSTEM. |
| | PLEASE SUBMIT. |
| | |
| | 6) NOTE: PLEASE SEE MISSING DISCONNECT FOR FEEDERS FROM |
| | THE GENERATOR TO MEET 225.31-225.39. |
| | PLEASE KNOW AS ZONING WILL REQUIRE AN ENCLOSURE AROUND |
| | THE UNIT AND THE GENERATOR BREAKER MAY NOT BE USED TO |
| | MEET 702.11AS THIS WILL BE ENCLOSED, ETC, PLEASE |
| | PROVIDE DISCONNECT. |
| | PLEASE SEE COMMENT ABOVE WITH RESPECT TO THE TYPE OF |
| | ATS. THIS NEED ONLY BE A DISCONNECTING MEANS AND DOES |
| | NOT REQUIRE OVER CURRENT PROTECTION. |
| | |
| | 7) NOTE: PLEASE SEE NOTE ON SHEET EE-001WHICH MENTIONS |
| | OWNER MAY CHOOSE LOADS MANUALLY PER 702.5, HOWEVER THE |
| | SYSTEM AS SUBMITTED IS AN AUTOMATED SYSTEM. |
| | PLEASE CLARIFY. |
| | |
| | THE LIFE SAFETY CODE ALONG WITH STATUTES ETC REQUIRED |
| | EMERGENCY AND LEGALLY REQUIRED SYSTEMS. IT IS WITH |
| | RESPECT TO SECTION 702 FOR OPTIONAL STAND-BY SYSTEMS, |
| | THE CODES ETC DO NOT REQUIRE ANY SUCH SPECIFIC LOADS |
| | AND THE LOADS FOR AN OSS MAY BE CHOSEN BY OWNER. AS THE |
| | PLANS SHOW A COMPLETE AUTOMATED SYSTEM, THIS UNIT SHALL |
| | MEET ALL LOADS AS DETERMINED BY LOAD CALCULATIONS OR |
| | BUILDING READINGS AS STATED. NO MANUAL SYSTEM WAS SHOWN |
| | ON PLANS. |
| | PLEASE PROVIDE MORE DETAILS ON LOADS WHICH WERE |
| | GENERATED BY READINGS. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE 60AMP CIRCUIT WHICH IS |
| | SHOWN ON RISER BEING FED FROM A *OWNER APPROVED |
| | PANEL*??? |
| | THIS FEED ON THE SHEET E4-002 APPEARS THIS IS COMING |
| | FROM ANOTHER SERVICE/LOCATION. |
| | AS SYSTEM TO SINGLE UNIT EQUIPMENT MAY NOT BE MIXED |
| | FROM DIFFERENT SERVICES, UNTIL CLARIFICATION IS MADE NO |
| | REVIEW FOR THIS ITEM CAN BE CONFIRMED. |
| | PLEASE ALSO INDICATE WHAT THIS CIRCUIT IS FOR? |
| | PLEASE PROVIDE LOADS, ETC. |
| | FBC 106.1.2 |
| | |
| | ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR |
| | REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS |
| | SUBMITTED. |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |