Plan Review Notes
Plan Review Notes For Permit 07090490
Permit Number 07090490
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-14 13:49:27** DENIED**
  
 1) NOTE: PLEASE SUBMIT TWO SETS OF PLANS. PLEASE DO NOT
 SUBMIT INDIVIDUAL LOOSE SHEETS NOT IN SETS FOR REVIEW.
 ONE SET WAS MADE FOR REVIEW OF PLANS BY THIS REVIEWER.
 PLEASE BE SURE TO DO THIS UPON THE NEXT RE-SUBMITTAL OF
 PLANS.
 FBC ADMIN SECTION 106.1
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED.
  
 3) NOTE: PLEASE SEE COLOR CODING IS REQUIRED TO BE
 BROWN, PURPLE AND YELLOW.
 THE NEC DOES NOT PROVIDE COLOR CODING AND *ORANGE* IS
 BASED ON A HIGH-LEG SYSTEM WHICH THIS IS NOT. THE
 CURRENT COLOR CODING IN THIS JURISDICTION FOR THE PAST
 20+ YEARS IS THAT AS BR/PURP/YELL.
 90.4
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR BOTH THE GENERATOR AND ATS BEING PROPOSED.
 PLEASE SEE COMMENTS BELOW AS THERE ARE SEVERAL ITEMS TO
 BE REVIEWED FOR CODE COMPLIANCE WHICH CAN NOT BE DONE
 AT THIS TIME.
 PLEASE BE SURE THE SPECS/CUT SHEETS FOR ANY FUEL TANK
 FOR PRIME-MOVER ARE SUBMITTED ALSO. THIS WILL BE
 REVIEWED BY OTHER TRADES SUCH AS MECHANICAL, FIRE
 MARSHAL ETC.
 NEC 90.7, 110.3 ETC
  
 5) NOTE: PLEASE SEE 240.13 AND 230.95 AS GF PROTECTION
 COULD NOT BE LOCATED.
 PLEASE ALSO SEE SPECIFICATIONS FROM MANUFACTURES AS
 THIS MAY REQUIRE THIS TO BE A 4-POLE DEVICE WHICH THE
 GENERATOR WOULD THEN BECOME AND SEPARATELY DERIVED
 SYSTEM.
 PLEASE SUBMIT.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECT FOR FEEDERS FROM
 THE GENERATOR TO MEET 225.31-225.39.
 PLEASE KNOW AS ZONING WILL REQUIRE AN ENCLOSURE AROUND
 THE UNIT AND THE GENERATOR BREAKER MAY NOT BE USED TO
 MEET 702.11AS THIS WILL BE ENCLOSED, ETC, PLEASE
 PROVIDE DISCONNECT.
 PLEASE SEE COMMENT ABOVE WITH RESPECT TO THE TYPE OF
 ATS. THIS NEED ONLY BE A DISCONNECTING MEANS AND DOES
 NOT REQUIRE OVER CURRENT PROTECTION.
  
 7) NOTE: PLEASE SEE NOTE ON SHEET EE-001WHICH MENTIONS
 OWNER MAY CHOOSE LOADS MANUALLY PER 702.5, HOWEVER THE
 SYSTEM AS SUBMITTED IS AN AUTOMATED SYSTEM.
 PLEASE CLARIFY.
  
 THE LIFE SAFETY CODE ALONG WITH STATUTES ETC REQUIRED
 EMERGENCY AND LEGALLY REQUIRED SYSTEMS. IT IS WITH
 RESPECT TO SECTION 702 FOR OPTIONAL STAND-BY SYSTEMS,
 THE CODES ETC DO NOT REQUIRE ANY SUCH SPECIFIC LOADS
 AND THE LOADS FOR AN OSS MAY BE CHOSEN BY OWNER. AS THE
 PLANS SHOW A COMPLETE AUTOMATED SYSTEM, THIS UNIT SHALL
 MEET ALL LOADS AS DETERMINED BY LOAD CALCULATIONS OR
 BUILDING READINGS AS STATED. NO MANUAL SYSTEM WAS SHOWN
 ON PLANS.
 PLEASE PROVIDE MORE DETAILS ON LOADS WHICH WERE
 GENERATED BY READINGS.
  
 8) NOTE: PLEASE CLARIFY THE 60AMP CIRCUIT WHICH IS
 SHOWN ON RISER BEING FED FROM A *OWNER APPROVED
 PANEL*???
 THIS FEED ON THE SHEET E4-002 APPEARS THIS IS COMING
 FROM ANOTHER SERVICE/LOCATION.
 AS SYSTEM TO SINGLE UNIT EQUIPMENT MAY NOT BE MIXED
 FROM DIFFERENT SERVICES, UNTIL CLARIFICATION IS MADE NO
 REVIEW FOR THIS ITEM CAN BE CONFIRMED.
 PLEASE ALSO INDICATE WHAT THIS CIRCUIT IS FOR?
 PLEASE PROVIDE LOADS, ETC.
 FBC 106.1.2
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
  
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  