| Date |
Text |
| 2007-11-02 09:51:05 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 & |
| | R4101 SWIMMING POOLS. |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE |
| | RESUBMITTED PLANS: |
| | |
| | 1. SHEET 2, EQUIPMENT LAYOUT: ANY HAND WRITTEN CHANGES |
| | TO THE PLANS IS UNACCEPTABLE UNLESS THEY ARE BY THE |
| | DESIGN PROFEFFIONAL OF RECORD RONALD GLORSKY P. E. |
| | #13220, AND HAVING HIS SIGNATURE AND DATE THE CHANGES. |
| | PER *106.1.3, QUALITY OF BUILDING PLANS. |
| | ** NOTE: ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH |
| | REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION |
| | 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. |
| | NOTE: A TRANSMITTAL LETTER IS HELPFUL. |
| | |
| | 2. SHEET 2, EQUIPMENT LAYOUT: WHITE OUT ON PLANS IS |
| | UNACCEPTABLE, NEW SHEETS REQUIRED. PER *106.1.3, |
| | QUALITY OF BUILDING PLANS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |