| 2008-03-10 15:33:02 | |
| | 1041 45TH ST 2ND REV.DOC |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07090466 |
| | ADD: 1041 45TH STREET |
| | CONT: NEUTRON ELECTRIC |
| | TEL: (561)201-5005 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 3RD 3-10-08 |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| | RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| | BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| | SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM |
| | BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME |
| | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| | 2004 FBC BUILDING WITH THE 2007 REVISIONS. |
| | |
| | 2) 3RDREQUEST, MISSING INFORMATION ON PLAN IN REGARDS |
| | TO WIND: 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE |
| | CONSTRUCTION DRAWINGS, 1)- BASIC WIND SPEED, MPH 2)- |
| | WIND IMPORTANCE FACTOR, & BUILDING CATEGORY3)- WIND |
| | EXPOSURE |
| | |
| | 3) 3RDREQUEST,2004 FBC 1609.1.3 PLEASE PROVIDE |
| | INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST |
| | THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING. |
| | GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE SIZE |
| | OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE |
| | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| | REQUIRES WITHOUT LOAD REDUCTION. |
| | |
| | THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL |
| | COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE |
| | DESIGNER. FL.S .S 481.229 (ARCHITECT) OR FL.S.S 471.003 |
| | (ENGINEER). THIS AREA IS IN A FLOOD ZONE AH; THEREFORE |
| | THE ELEVATION OF THE CONCRETE SHALL BE A MINIMUM OF |
| | 17'6", WHICH SHALL BE STATED OF THE ENGINEERED PLANS. |
| | ALL DIMENSIONS FOR THE CONCRETE SLAB SHALL BE INDICATED |
| | ON THE DRAWINGS INCLUDING THE THICKNESS. INDICATE THE |
| | CLEARANCE AROUND THE GENERATOR FOR MAINTENANCE AND |
| | REPAIR WORK. |
| | |
| | **NOTE** IN ORDER TO PROVIDE CONFORMITY TO OUR RECORD |
| | RETENTION PROGRAM 'NO WHITE-OUT OR HANDWRITING IN PEN |
| | OR PENCIL' ON THE DRAWINGS OR REPORTS WILL BE |
| | ACCEPTABLE. CLEARLY STATE IF THE GENERATOR IS USED FOR |
| | LIFE SAFETY ISSUES. |
| | |
| | BUILDING PLAN REVIEW |
| | MYRON JACOBS |
| | TEL: (561)805-6726 |
| | FAX: (561)805-6676 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |