| 2007-12-05 16:15:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | **PLEASE SEE THAT MOST COMMENTS FROM THE PREVIOUS GAS |
| | PLAN REVIEW REMAIN. |
| | |
| | 1. NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND |
| | DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY. |
| | PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND |
| | NOT IN SETS. PER *106.3.1, APPROVAL OF CONSTRUCTION |
| | DOCUMENTS AND *106.1.2 ADDITIONAL DATA. |
| | |
| | 2. PROVIDE TWO (2) COPIES OF A SITE PLAN OR SURVEY |
| | THAT CLEARLY INDICATES THE PROPOSED LOCATION OF THE |
| | GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES |
| | AND ADJACENT DWELLING STRUCTURES. |
| | **NOTE: COMMENT NOT ADDRESSED. |
| | |
| | 3. OK, COMMENT ADDRESSED. |
| | |
| | 4. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NOTE: COMMENT NOT ADDRESSED. |
| | |
| | 5. WHAT TYPE OF GAS GAS IS BEING USED. (LP OR |
| | NATURAL) |
| | **NOTE: COMMENT IS ADDRESSED IN THE SUBMITTED |
| | MANUFACTURE SPECIFICATIONS BY INDICATING GENERATOR IS A |
| | DUEL FUEL GENERATOR. HOWEVER THERE ARE NO ISOMETRIC GAS |
| | RISER DIAGRAMS SUBMITTED TO INDICATE GENERATOR IS DUEL |
| | FUEL. |
| | |
| | 6. OK, COMMENT ADDRESSED. |
| | |
| | 7. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **NOTE: COMMENT NOT ADDRESSED. THERE WERE NO GAS |
| | ISOMETRIC RISER DIAGRAMS IN THE RESUBMITTAL. |
| | |
| | 8. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | **NOTE: COMMENT NOT ADDRESSED. |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | IF GAS DELIVERY PRESSURE IS GREATER THAN 2 PSI PLEASE |
| | SUBMIT TWO (2) COPIES OF THE MP REGULATORS BEING USED |
| | WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A |
| | LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | **NOTE: COMMENT NOT ADDRESSED. |
| | |
| | 10. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED |
| | MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING |
| | GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP |
| | TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW |
| | OR EXISTING ON THE RESUBMITTAL. |
| | |
| | 11. 11. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 6.6.1. |
| | NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED |
| | MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING |
| | GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP |
| | TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW |
| | OR EXISTING ON THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |